User`s manual
12
13
English
REPLACING THE BATTERY
WARNING!
This Uninterruptible Power Supply contains potentially hazardous
voltages. Do not attempt to disassemble the UPS beyond battery
replacement procedures below. This UPS contains no
user serviceable parts. Repairs and Battery replacement must
be performed by AUTHORIZED SERVICE PERSONNEL ONLY.
Do not open or mutilate batteries. Released electrolyte is harmful
to the skin and eyes and may be toxic.
CAUTION:
(AUTHORIZED SERVICE PERSONNEL ONLY)
CAUTION:
Do not dispose of batteries in a fire. The batteries may explode.
The batteries in this UPS are recyclable. Dispose of the batteries
properly. The batteries contain lead and pose a hazard to the
environment and human health if not disposed of properly. Refer
to local codes for proper disposal requirements or return the
battery to MINUTEMAN.
Although battery system voltages are only 12VDC, 24VDC, and
36VDC the battery system can still present a risk of electrical
shock. The current capability of a battery is sufficient to burn wire
or tools very rapidly, producing molten metal. Observe these
precautions when replacing the batteries:
1. Remove watches, rings, or other metal objects.
2. Use hand tools with insulated handles.
3. Wear protective eye gear (goggles), rubber gloves and boots.
4. Do not lay tools or other metal parts on top of batteries.
5. Disconnect the charging source prior to connecting or
disconnecting the battery terminals.
6. Determine if the battery is inadvertently grounded. If the
battery is, remove the source of the grounding. Contact with
any part of a grounded battery can result in an electrical shock.
The likehood of such shock will be reduced, if such grounds
are removed during installation and maintenance.
CAUTION:
English
Possible Cause
Symptom
What To Do
Press and release the On/Off/
Test button to start UPS
On/Off/Test button not
pushed
UPS will not turn on
Reset circuit breaker by
pressing the plunger back in.
If the AC circuit breaker trips
after UPS starts up, reduce
the load on the UPS
UPS operates in
battery mode only,
even though there is
normal AC present
Input AC circuit breaker is
tripped
UPS has detected an
internal fault
Call for service
Fault LED is
illuminated
The On-line/On-
Battery LED is
illuminated, but
there is no output
Incorrect service wiring
Disconnect the computer
cable from the UPS and press
the On button. If UPS works
normally, the software has
control of the UPS
The UPS is being
controlled via its
communications port
Site Wiring Fault
LED is illuminated
Have a Qualified Electrician
correct the service wiring
The batteries may be weak
or at the end of useful
service life
Charge the batteries for 8
hours and retest. If the runtime
is still less than expected, the
batteries may need to be
replaced, even though the
Weak/Bad Battery LED is not
illuminated
UPS does not
provide expected
runtime
Weak/Bad Battery
LED is illuminated
Overload LED is
illuminated and a
constant alarm
The On-Line LED is
blinking and the au-
dible alarm is silent
UPS occasionally
emits a beep
Weak/bad batteries or bad
connections at the battery
Normal operation
The load has exceeded the
UPS's capacity
The UPS is in either the
Boost mode or the Buck
mode
Check battery connections,
charge the batteries for 8
hours, replace the batteries
The UPS is performing its
intended function
Check the specifications (see
section 8). Remove part of the
load
The UPS is performing its
intended function
The PRO-E Series UPS has an easy to replace hot-swappable batteries. Please
read all of the WARNINGS and CAUTIONS before attempting to service the
batteries.
NOTE: If there is a power interruption while replacing the hot-swappable
batteries, with the UPS on, the load will not be backed up.










