Specifications

System Components
4
System Components
Panel Models
Model Description
FX-350-60-R/DR,
FX-350-126-R/DR
FX-350-378-DR
Multi-zone fire alarm control panel with 2 x 20 LCD
display, one (Style Y or Style D) analog loop (60 or
126 devices), or three loops (378 devices), four
Power Limited Class B (Style Y) indicating circuits
(max 1.7 Amps each - 5 Amps total), and dedicated
common alarm, supervisory, trouble, and auxiliary
alarm relays.The model with suffix DR has a two
line UDACT Digital Communicator and modem
included. An optional OCAC-304 Class A converter
module may be used to convert the indicating
circuits to Class A (Style Z). Additional outputs
include connections for a RTI remote trouble
indicator, PR-300 Reverse Polarity Module, an RS-
485 bus for connection of up to seven RAM-
300LCDs, SRM-312s and RA-1000 Series
annunciators. Auxiliary power is available in the
form of 24V FWR unfiltered and unsupervised,
24VDC filtered and regulated, and resettable
auxiliary power supply.
The panel is available with a red door.
Model Description
FX-351-LW,
FX-351-LDW
Multi-zone fire alarm control panel with 2 x 20 LCD
display and 32 LED display, one (Style Y or Style D)
analog loop (126 devices), four Power Limited
Class B (Style Y) indicating circuits (max 1.7 Amps
each - 5 Amps total), and dedicated common
alarm, supervisory, trouble, and auxiliary alarm
relays. An optional additional RAX-332 Display
Adder can be added to provide 64 annunciation
points. A two line UDACT Digital Communicator
and modem is included with Model FX-351-LDW.
An optional OCAC-304 Class A converter module
may be used to convert the indicating circuits to
Class A (Style Z). Additional outputs include
connections for a RTI remote trouble indicator, PR-
300 Reverse Polarity Module, an RS-485 bus for
connection of up to seven RAM-300LCDs, SRM-
312s and RA-1000 Series annunciators. Auxiliary
power is available in the form of 24V FWR
unfiltered and unsupervised, 24VDC filtered and
regulated, and resettable auxiliary power supply.
The panel is available with a white door.
COMMON ALARM
COMMON SUPV
COMMON
TROU BLE
CPU FAULT
GROUND
FAULT
SYSTEM
RESET
FIRE
DRILL
ALARM
ACKNOWLEDGE
GENE RAL
ALARM
SIGNAL
SILENCE
BUZZE R
SILENCE
LAMP
TES T
SPARE
AC ON
1 2
ABC
3
DEF
5
JKL
6
MNO
7 8
TUV
9
WXY
* 0
QZ
#
4
GHI
PRS
X
M
?
SYSTEM NORMAL
MAY 21, 2006 02:41PM
FX-350 SERIES
Fire Alarm Control Panel
SYSTEM
RESET
FIRE
DRIL L
ALARM
ACKNOWLE DGE
GENERAL
ALARM
SIGNAL
SILENCE
BUZZ ER
SILENCE
LAMP
TEST
SPARE
AC ON
1 2
ABC
3
5 6
7 8 9
* 0 #
4
X
M
?
DEF
GHI JKL MNO
PRS
TUV
WX Y
QZ
COMMON ALARM
COMMON SUPV
COMMON TROUBL E
CPU FAUL T
GROUND FAUL T
SYSTEM NORMAL
OCT 21, 2005 10:25AM
ZO N E -1
ZO N E -1
ZO N E -1
ZO N E -1
ZO N E - 1
ZO N E - 1
ZO N E - 1
ZO N E - 1
ZO N E -1
ZO N E -1
ZO N E -1
ZO N E -1
ZO N E - 1
ZO N E - 1
ZO N E - 1
ZO N E - 1
ZO N E -1
ZO N E -1
ZO N E -1
ZO N E -1
ZO N E - 1
ZO N E - 1
ZO N E - 1
ZO N E - 1
ZO N E -1
ZO N E -1
ZO N E -1
ZO N E -1
ZO N E - 1
ZO N E - 1
ZO N E - 1
ZO N E - 1
FX-350 SERIES
Fire Alarm Control Panel