Specifications
FX-350 Series Installation and Operation Manual
5
Output Class A converter: four circuits
Polarity reversal/city tie
M o d e l   Description
FX-353-LDR
FX-353-LDW
Multi-zone fire alarm control panel with 2 x 20 
LCD display and 32 LED display, three (Style 
Y or Style D) analog loops (378 devices), four 
Power Limited Class B (Style Y) indicating 
circuits (max 1.7 Amps each - 5 Amps total), 
and dedicated common alarm, supervisory, 
trouble, and auxiliary alarm relays. An 
optional additional RAX-332 Display Adder 
can be added to provide 64 annunciation 
points. A two line UDACT Digital 
Communicator and modem is included. An 
optional OCAC-304 Class A converter 
module may be used to convert the indicating 
circuits to Class A (Style Z). Additional 
outputs include connections for a RTI remote 
trouble indicator, PR-300 Reverse Polarity 
Module, an RS-485 bus for connection of up 
to seven RAM-300LCDs, SRM-312s and RA-
1000 Series annunciators. Auxiliary power is 
available in the form of 24V FWR unfiltered 
and unsupervised, 24VDC filtered and 
regulated, and resettable auxiliary power 
supply. The panel is available with a red or 
white door.
Model Description
OCAC-304
Output Class A converter module (four 
circuits)
Model Description
PR-300
Polarity Reversal and/or City 
Tie Module
SYSTEM
RESET
FIRE
DRIL L
ALARM
ACKNOWLE DGE
GENERAL
ALARM
SIGNAL
SILENCE
BUZZ ER
SILENCE
LAMP
TEST
SPARE
AC ON
1 2
ABC
3
5 6
7 8 9
* 0 #
4
X
M
?
DEF
GHI JKL MNO
PRS
TUV
WX Y
QZ
COMMON ALARM
COMMON SUPV
COMMON TROUBL E
CPU FAUL T
GROUND FAUL T
 SYSTEM NORMAL
OCT 21, 2005 10:25AM
ZO N E -1
ZO N E -1
ZO N E -1
ZO N E -1
ZO N E - 1
ZO N E - 1
ZO N E - 1
ZO N E - 1
ZO N E -1
ZO N E -1
ZO N E -1
ZO N E -1
ZO N E - 1
ZO N E - 1
ZO N E - 1
ZO N E - 1
ZO N E -1
ZO N E -1
ZO N E -1
ZO N E -1
ZO N E - 1
ZO N E - 1
ZO N E - 1
ZO N E - 1
ZO N E -1
ZO N E -1
ZO N E -1
ZO N E -1
ZO N E - 1
ZO N E - 1
ZO N E - 1
ZO N E - 1
FX-350 SERIES
Fire Alarm Control Panel
- SIG1 OUT+- SIG2 OUT+
- SIG1 RET+- SIG2 RET+
BLK RED
BLK RED
- SIG3 OUT+- SIG4 OUT+
- SIG3 RET+- SIG4 RET+
BLK RED
BLK RED
POLARITY
REVER SAL
ALARM
POLARITY
REVER SAL
SUPV
CIT Y
TIE
+ |   - + |   - + |   -
JW4
P1 P2
Mounting hol e for
#6 -32 scr ews
Mounting hol e for
# 6-32 scr ews