Specifications
Appendix B: Reporting
42
Appendix B: Reporting
Ademco Contact-ID 
FX-350 Series Event Codes 
Description 
Event
Family
Qualifier  Code Group # Contact #
Phone Line #1 trouble detected  Trouble New event  1 351 00 000
Phone Line #2 trouble detected  Trouble New event  1 352 00 000
Phone Line #1 trouble restored  Trouble Restore  3 351 00 000
Phone Line #2 trouble restored  Trouble Restore  3 352 00 000
Failure to report to an Account  Trouble New event  1 354 Acct # Acct #
Report to an Account successful  Trouble Restore  3 354 Acct # Acct #
RS-485 Communication Trouble  Trouble New event  1 350 00 485
Periodic (24 hr) Test Event (NORMAL)  Test New event  1 602 00 000
Periodic (24 hr) Test Event (OFF NORMAL)  Test New event  1 608 00 000
Manually initiated dialer test  Test New event  1 601 00 000
Zone Fire Alarm  Alarm New event  1 110 00 NNN
Zone Fire Alarm restored  Alarm Restore  3 110 00 NNN
Zone Trouble detected  Trouble New event  1 300 00 NNN
Zone Trouble restored  Trouble Restore  3 300 00 NNN
Zone Supervisory condition  Supervisory New event  1 200 00 NNN
Zone Supervisory restored  Supervisory Restore  3 200 00 NNN
Water flow  Alarm New event  1 113 00 NNN
Water flow restored  Alarm Restore  3 113 00 NNN
Indicating Zone Trouble  Trouble New event  1 320 00 NNN
Indicating Zone Trouble restored  Trouble Restore  3 320 00 NNN
General Alarm  Alarm New event  1 140 00 NNN
General Alarm restored  Alarm Restore  3 140 00 NNN
AC power lost  Trouble New event  1 301 00 000
AC power restored  Trouble Restore  3 301 00 000
Battery Low  Trouble New event  1 302 00 000
Battery Low restored  Trouble Restore  3 302 00 000
Ground Fault  Trouble New event  1 310 00 000
Ground Fault restored  Trouble Restore  3 310 00 000