Specifications
FX-350 Series Installation and Operation Manual
45
Appendix D: Power Supply and Battery Calculations
POWER REQUIREMENTS (ALL CURRENTS ARE IN AMPERES)
Model Number Description Qty STANDBY  TOTAL
STANDBY 
ALARM TOTAL
ALARM 
FX-350-60-R/
FX-350-126-R
Main Panel 
X
0.200
=
0.370
=
FX-350-60-DR/
FX-350-126-DR
FX-350-378-DR
Main Panel c/w Dialer
X
0.220
=
0.380
=
FX-351-LW
Main Panel c/w 1 RAX-
332 LED Displays
 X
0.210
=
0.390 (Note 1)
=
FX-351-LDW/
FX-353-LDR/
FX-353-LDW
Main Panel, c/w 1 RAX-
332 LED Displays and 
Dialer
X
0.230
=
0.400 (Note 1)
=
ALC-252
252 Point Dual Loop 
Addressable Adder
x
0.120
=
0.230
=
RAX-332  32 LED Display
X
0.005
=
0.010
=
PR-300
Polarity Reversal and 
City Tie Module
X
0.050
=
0.300
=
RAM-300-
LCDW/R
Remote LCD 
Annunciator
X
0.016
=
0.040
=
RAM-208/216
Remote Annunciator, 8 
Zone LED
X
0.0350
=
0.090
=
RTI-1
Remote Trouble 
Indicator
X
0.035
=
0.035
=
MIX-3000 Ionization Detector
X
0.00028
=
0.00028
=
MIX-3100 Photoelectric Detector
X
0.00034
=
0.00034
=
MIX-3200 Multi-sensor Detector
X
0.00047
=
0.00047
=
MIX-3300 Heat Detector
X
0.00025
=
0.00025
=
MIX-100P Priority Monitor Module
X
0.00060
=
0.00060
=
MIX-101P
Mini Priority Monitor 
Module
X
0.00060
=
0.00060
=
55000-820
Relay Output Module
X
0.00085
=
0.00085
=
MIX-100S
Supervised Control 
Module
X
0.00100
=
0.00100
=
MIX-100X (Kit)
100XH (Isolator)
100XB (Base)
Isolator c/w Mounting 
Base
X
0.000035
=
0.000035
=
MIX-2001R Relay Base
X
0.000002
=
0.000040
=
Device & Remote LEDs (Maximum 30)   X 0.0040
=
Signal Load (bells, horns, strobes, and etc.)
 X
=
Auxiliary Power Supply for Annunciators, etc. (See Note 2)
==
Total currents (Add above currents)     STANDBY(A) ALARM (B)
=