Specifications

106
Appendix D: Specifications
Aux Relay Form C, 1 A max, 28 VDC
Unfiltered supply
(full wave rectified)
Power limited / Unregulated / Special Application
1.7A Max, 21.3 VDC to 42.00 VDC
Minimum Load 5mA
Battery Type
24VDC Gel Cell/Sealed lead acid – 10AH to 26AH
Charging capability
10AH to 26AH
Current Consumption standby: 200 mA
alarm: 350 mA
Protection
10A on board (F1) slow blow micro fuse
Compliance System Model FR-320 Series Control Unit - Fire Alarm, for
Releasing services
System Type Local Auxiliary (using PR-300), Remote Protected
Premises Station (using PR-300 or FR-320-DR/DW).
Central Station Protected Premises (using FR-320-
DR/DW.) For ULC application also use PR-300 for
alternate communication path.
Type of Service A, M, WF, SS
Type of Signalling Non-Coded
Applicable Standards NFPA 12, 12A, 12B, 12, 15, 16,70,72,2001, UL-864
Rev. 9, ULC S-524, ULC S-527-99
Table 8 FR-320 System Modules and Annunciators
FR-320
System Modules and Annunciators
RM-306 Relay Adder Module Must be connected to a listed power-limited
source of supply.
Contact rating FormC/ 28VDC per contact / 1A resistive load
max, zoned
Current consumption standby 0mA, alarm 80mA
ICAC-306 Input Class A Converter module standby: 0mA / alarm: 0mA
OCAC-304 Output Class A Converter Module standby: 0mA / alarm: 0mA
Table 7 FR-320 Series Specifications (Continued)
FR-320 Series Fire Control Panel Chassis