Appendix E: Power Supply and Battery Calculations
17.0 Appendix E: Power Supply and
Battery Calculations
Use the form below to determine the required secondary power supply (batteries).
* Assume three Initiating Circuits are in alarm.
' Use 0.084 for five minutes, 0.168 for 10 minutes and 0.5 for 30 minutes of alarm as a multiplier figure.
Ò Using the Mircom MPD-65P 2-wire photoelectric smoke detector. See 14.0 Appendix B: FR-320 Series
Compatible Devices on page 98 for other compatible smoke detectors.
Total Current Requirement: ALARM (B)______ Amps. (Value obtained from column B)
IMPORTANT NOTICE
The main AC branch circuit connection for Fire Alarm Control Panel must provide a dedicated continuous power without provision of any
disconnect devices. Use #12 AWG wire with 600-volt insulation and proper over-current circuit protection that complies with the local codes.
Refer to 16.0 Appendix D: Specifications on page 105 for specifications.
POWER REQUIREMENTS (ALL CURRENTS ARE IN AMPERES)
Model Number Description Qty Standby Total Standby Alarm Tota l
Alarm
FR-320(-R/W)
Pre-Action/Deluge and
Agent Release Control
Panel FIXED ELR/ACTIVE
ELR
X 0.123/0.092
=
0.316/
0.292
=
FR-320-DR/
DW
Pre-Action/Deluge and
Agent Release Control
Panel FIXED ELR/ACTIVE
ELR with dialer
X 0.123/0.100
=
0.318/
0.300
=
ICAC-306
Det Class A Converter
Adder Module
X 0.000
= 0.000 =
OCAC-302
Sig Class A Converter
Adder Module--2 Circuits
X 0.000
= 0.000 =
PR-300
Polarity Reversal and City
Tie Module
X 0.050
= 0.300 =
RM-306 6 Relay Adder Module X 0.000
= 0.080 =
SRM-312
12 Relay Smart Relay
Module
X 0.030
=0.140=
RAM-208/216 Remote Annunciators X 0.035
=0.090=
RTI-1 Remote Trouble Indicator X 0.035
=0.035=
Two-Wire Smoke Detectors X Ò 0.00011
= * 0.135 =
Four-Wire Smoke Detectors X
= =
Signal Load (bells, horns, strobes, and etc.) X
=
Auxiliary Power Supply for Annunciators, etc.
=
=
Total currents (Add above currents) STANDBY
(A)
ALARM
(B)