Specifications
17
System Components
4.0  System Components
4.1  Main Pre-Action/Deluge and Agent Release Control Panel
The following models are part of the FR-320 Series:
• FR-320
• FR-320-W
• FR-320-R
• FR-320-DW
• FR-320-DR
Figure 1 FR-320 Panel
All FR-320 Panels have the following features:
• Six Zone Pre-Action/Deluge and Agent Release Control Panel with LED display (red or 
white door, black box.
• six Class B (Style B) initiating circuits, and four Class B (Style Y) output circuits
• Output circuits 1 & 2 are Class B (Style B) indicating circuits that can be converted to 
Class A (Style Z) using an OCAC-302 Output Class A Converter adder module.
• Output circuits 3 & 4 are Class B (Style B) only releasing circuits.
• Each output circuit can draw 1.7A current, 5A total. A six zone ICAC-306 Input Class A 
Converter adder module may be used for Class A (Style D) wiring of Initiating circuits.
• The FR-320 contains Common Alarm, Common Supervisory & Common Trouble 
Relays, auxiliary alarm relay (disconnectable), an RS-485 Interface for Remote 
Annunciators and a Resettable Four Wire Smoke Detector Power Supply.
• Two batteries are required.
Additionally:
• FR-320-DW/R panels contain a dialer.
• FR-320 uses a BBX-1024DS or BBX-1024DSR enclosure. 