Specifications

29
Field Wiring
7.2 Abort and Manual Release Switch Wiring
Wiring for the abort and manual release switches is shown in Figures 10 and 11. Depending
on the selected mode, the Abort and Manual release switches can either be on different
circuits or they both can be on the same circuit. When on separate circuits, DET5 is used for
the Abort switch and DET6 is used for the manual release switch. When on the same circuit,
DET 5 Abort/Manual release combination is for hazard area 1, while DET6 Abort/Manual
release combination is for hazard area 2. When an Abort/Manual release combination is used,
ensure that the Manual release switch is always before the Abort switch. Also ensure that
there is a current limiting resistor (MP-1500R/W) between the Manual release and Abort
switch for differentiating between the two switches.
Figure 13 Abort and Manual Release Switch Class B or Style B Wiring
Note: For the circuit with the combined Abort Switch and Manual Release Switch, a
maximum of four Abort Switches can be connected.
3.9K 1/2 WATT ELR
OR ELRX-300 /R
FIRE ALARM MAIN BOARD
+
-
+
-
DET 5DET 6
INITIATING
CIRCUIT #5
INITIATING
CIRCUIT #6
FIRE ALARM MAIN BOARD
+
-
+
-
DET 5
DET 6
INITIATING
CIRCUIT #5
INITIATING
CIRCUIT #6
Current limiter
MP -1500 R/W
3.9K 1/2 WATT ELR
OR ELRX-300 /R
3.9K 1/2 WATT ELR
OR ELRX-300 /R
MANUAL RELEASE
SWITCH
Use MS-403,404
USE ONLY NO
CONTACT
ABORT SWITCH
CONNECT A UL/ULC LISTED ABORT STATION ACCEPTABLE TO
THE AHJ, COMPLYING WITH THE FOLLOWING SPECIFICATIONS:
MAXIMUM IMPEDENCE = 1.4K OHMS
RATED CURRENT = 45mA
RATED VOLTAGE= 24V
Abort and Manual Release switches on a combined circuit
Abort and Manual Release switches on separate circuits
Current limiter
MP-1500 R/W
Note: Maximum 4 Abort Switches
can be connected on each
combined Manual Release and
Abort Switch circuit.
Current limiter
MP-1500 R/ W
Current limiter
MP -1500 R/W
3.9K 1 /2 WATT ELR
OR ELRX-300/R