Specifications

30
Field Wiring
Figure 14 Abort and Manual Release Switch Class A or Style D Wiring
FIRE ALARM MAIN BOARD
+
-
+
-
DET 5DET 6
INITIATING
CIRCUIT #5
INITIATING
CIRCUIT #6
FIRE ALARM MAIN BOARD
+
-
+
-
DET 5
DET 6
INITIATING
CIRCUIT #5
INITIATING
CIRCUIT #6
Current limiter
MP -1500 R/W
MANUAL RELEASE
SWIT CH
USE MS -403 ,404
USE ONLY NO
CONTACT
ABORT SWITCH
CONNECT A UL /ULC LISTED ABORT STATION
ACCEPTABLE TO THE AHJ, COMPLYING WITH THE
FOLLOWING SPECIFICATIONS :
MAXIMUM IMPEDENCE = 1.4K OHMS
RATED CURRENT = 45mA
RATED VOLTAGE= 24V
Abort and Manual Release switches on a combined circuit
Abort and Manual Release switches on separate circuits
Current limiter
MP-1500 R/W
Note: Maximum 4 Abort
Switches can be connected
on each combined Manual
Release and Abort Switch circuit.
Current limiter
MP-1500 R/W
Current limiter
MP -1500 R/W
BLK RED
BL K R ED
-DET5 OUT+-DET6 OUT+
-DET5 RET+-DET6 RET+
BLK RED
BL K R ED
- DET5 OUT+-DET6 OUT+
-DET5 RET+-DET6 RET+
ICAC-306
CLASS A
CONVERTER
MODULE
ICAC-306
CLASS A
CONVERTER
MODULE