Specifications
30
Field Wiring
Figure 14  Abort and Manual Release Switch Class A or Style D Wiring
FIRE ALARM MAIN BOARD
+
-
+
-
DET 5DET 6
INITIATING
CIRCUIT #5
INITIATING
CIRCUIT #6
FIRE ALARM MAIN BOARD
+
-
+
-
DET 5
DET 6
INITIATING
CIRCUIT #5
INITIATING
CIRCUIT #6
Current limiter
MP -1500 R/W
MANUAL RELEASE 
SWIT CH
USE MS -403 ,404
USE ONLY NO 
CONTACT
ABORT SWITCH
CONNECT A UL /ULC LISTED ABORT STATION 
ACCEPTABLE TO THE AHJ, COMPLYING WITH THE 
FOLLOWING SPECIFICATIONS :
MAXIMUM IMPEDENCE  = 1.4K OHMS
RATED CURRENT = 45mA
RATED VOLTAGE= 24V
 Abort and Manual Release switches on a combined circuit
Abort and Manual Release switches on separate circuits
Current limiter
MP-1500 R/W
Note: Maximum 4 Abort 
Switches can be connected 
on each combined Manual 
Release and Abort Switch circuit.
Current limiter
MP-1500 R/W
Current limiter
MP -1500 R/W
BLK RED
BL K  R ED
-DET5 OUT+-DET6 OUT+
-DET5 RET+-DET6 RET+
BLK RED
BL K  R ED
- DET5 OUT+-DET6 OUT+
-DET5 RET+-DET6 RET+
ICAC-306
CLASS A 
CONVERTER 
MODULE
ICAC-306
CLASS A 
CONVERTER 
MODULE










