Specifications
35
Field Wiring
7.6.1 Power Supply Connection
The power supply is part of the Main Chassis. The ratings are:
Wire the power supply as shown below in Figure 19 using the proper wire gauge.
Figure 22 Power Supply Connection
Table 1 Power Supply Ratings
Type Rating
Electrical Input rating 120 VAC 60Hz 1.7A /240 VAC 50 Hz 0.85 A, 10A slow blow fuse on
secondary of transformer
Power supply total current
6.5A AC maximum @ secondary of transformer
Battery fuse on Main module
10A, slow blow micro fuse
Caution: Do not exceed power supply ratings.
!
BATTERY BATTERY
red
green
blk
yellow
P3
BA TTERY
P4
+
-
P1
P2
P6 P5
POWER SUPPLY
BUZZER
SILENCE
RAC2
(ZONE 4)
SPARE
RAC1
(ZONE 3)
P6
Deluge Panel Control Board
Power Supply Control Board
red
red
10A
slow blow
++
red
blk
NOTE: TO PREVENT SPARKING, CONNECT BATTERIES AFTER THE
SYSTEM MAIN A.C. POWER IS TURNED ON
240 VAC 50Hz
120 VAC 60Hz
N
GND