Field Wiring
7.9 Supervised Auxiliary Power (regulated)
Supervised auxiliary power is used to power the remote annunciators and smart relay
modules. This filtered circuit is supervised therefore a short will disconnect the power and the
common trouble is active. The power is reconnected after the 'RESET' key is pressed. See
16.0 Appendix D: Specifications on page 105 for supply rating.
7.10 Unfiltered Supply (full wave rectified)
This regulated supply is not supervised. If there is a short on this circuit, the auxiliary power
does not recover automatically when the short is removed. This power supply must be
disconnected, then reconnected and the panel reset to re-establish the auxiliary power supply.
See 16.0 Appendix D: Specifications on page 105 for supply rating.