Specifications

53
Configuration
Command Menu-->Panel Config-->Features
Command Menu-->Panel Config-->
Hazard Config
3. Man. Rls Delay
0->Default
Available options:
0, 5, 10, 15, 20, 25, 30
seconds
Use this function to set the time delay
of activation of corresponding
releasing circuit(s) after activation of
the manual release switch.
Value: 0 to 30 seconds in five-second
increments.
Command Menu-->Panel Config-->
Hazard Config
4. Soak timer
0->Default (continuous)
The selectable values are
in seconds: 0, 10, 20, 30,
40, 50, 60, 120(2min),
180(3min), 240(4min),
300(5min), 360(6min),
420(7min), 480(8min),
540(9min), 600(10min),
660(11min), 720(12min),
780(13min), 840(14min),
900(15min)
Use this function to set the length of
time for which the releasing circuit is
active. When the soak timer expires,
the control panel automatically shuts
off the activated releasing circuit.
0 seconds means that the soak timer
is disabled and the releasing circuit is
active continuously.
Note: Refer to 10.3 How to Use the Keypad to Program the FR-320 on page 49 for
detailed instructions on making menu selections.
Man. Rls Delay(sec):
0
Man. Rls Delay(sec):
0
-Panel Features-
1. Man. Sig. Sil
2. Wtr/Sprk. Retd
3. Aux Dis Corr
4. Sig-Sil Inh Tm
5. Aux Dis Alm&Sv
6. Auto Sil. Tmr
7. Rem. Annun.
8. Alm. Xmit. Sil.
9. Pwr Fail Tmr.
10. Com. Supv. Rly
11. Sig. Sil. Isol.
12. 1st Alarm Code
13. 2nd Alarm Code
14. Supv. Latching
15. Supv on NAC-2
16. Sig-Sil NAC