Specifications

54
Configuration
Command Menu-->Panel Config-->Features
1. Manual Sig. Silence
[X] ENABLE ->Default
[ ] DISABLE
Use this function to enable or
disable the Signal Silence
operation on the panel.
Command Menu-->Panel Config-->Features
2. Wtr/Sprk. Retd
[ ] ENABLE
[X] DISABLE->Default
By default all the initiating circuits
configured as waterflow or
sprinkler act as non-verified
alarms. If enabled, a retard
operation is performed for initiating
circuits configured as waterflow or
sprinkler.
Command Menu-->Panel Config-->Features
3. Aux Dis Corr
[X] ENABLE ->Default
[ ] DISABLE
By default this function will
disconnect the auxiliary alarm
relay when the aux disconnect
button is pressed. If enabled, this
function will disconnect the
auxiliary alarm relay and all
correlated relays when the aux
disconnect button is pressed.
Correlated relays include: RM-
306 and SRM-312.
Command Menu-->Panel Config-->Features
4. Sig-Sil Inh Tmr
[X] DISABLE->Default
[ ] 10sec
[ ] 20sec
[ ] 30sec
[ ] 1min
Use this function to inhibit the
signal silence switch for a desired
length of time. The time period
should expire before the signals
may be silenced. According to the
Canadian National Building Code,
this timer should be set to one
minute.
Command Menu-->Panel Config-->Features
5. Aux. Dis. Dis Alam&Sv
[ ] ENABLE
[X] DISABLE->Default
If enabled the Common Alarm and
Common Supervisory relays will
be disconnected when Aux.
Disconnect is pressed. Also, the
PR-300 will not transmit a
supervisory or alarm event.If
disabled, the Aux disconnect
switch has no effect on the
Common Alarm relay, the
Common Supervisory relay, and
the PR-300.
Command Menu-->Panel Config-->Features
6. Auto Sig-Sil. Tmr
[X] DISABLE->Default
[ ] 5 Min
[ ] 10 Min
[ ] 20 Min
[ ] 30 Min
Use this function to set the time
period for which the indicating
circuits will sound before they are
automatically silenced. According
to the Canadian National Building
Code, this timer should not be set
to less than 20 minutes.
Command Menu-->Panel Config-->Features
7. Rem. Annun.
[X] NONE->Default
[ ] 1
[ ] 2
...
[ ] 6
Use this function to program the
number of remote annunciators.
Any combination of remote
annunciators or smart relays can
be used as long as the number
does not exceed 6. The
annunciators’ addresses should be
linear: without gaps and in
sequence.
Man. Sig. Sil.
[X] ENABLE
Waterflow/Sprk Retd
[X] DISABLE
Aux Dis. Dis Corr
[X] ENABLE
Sig-Sil. Inhibi t Timer
[X] DISABLE
Aux Dis. Dis Alm&Sv
[X] DISABLE
Auto Sig-Sil. Tmr
[X] DISABLE
No. of Remote Annun.
[X] NONE