Specifications

64
Configuration
Command Menu-->Dialer-Config
10.10.4 Time Parameters
Command Menu/Dialer-Config/Report
Options
3. Supervisory priority
[X] Account 1->Default
[ ] Account 2
Use this function to set the account
priority for reporting supervisory
troubles. If the priority is set for
account#1 then the dialer will try
account#1 first for reporting.
Command Menu/Dialer-Config/Report
Options
4. Aux Disc Alm/Supv Rpt.
[ ] ENABLE
[X] DISABLE ->Default
If this function is enabled, the Aux
Disconnect feature (obtained by
pressing the Aux Disconnect button)
will block the alarm and supervisory
events from being reported through the
built-in dialer.
Note: Refer to 10.3 How to Use the Keypad to Program the FR-320 on page 49 for
detailed instructions on making menu selections.
Command Menu/Dialer-Config/Time
Parameter
1. AC Loss delay
0 ->Default
The AC loss delay
ranges from 0 to 20
hours
Use this function to delay the reporting of AC
loss trouble on the dialer for the programmed
time period. Press UP or DOWN button to
increase or decrease the number of hours.
Command Menu/Dialer-Config/Time
Parameter
2. Cellular report date
0 ->Default
The cellular report
date ranges from 0 to
28
Use this function to set the test report date
for the cell phone setup. If the date is set to
0, this means there is no test reporting for
cell phone or the phone line is a regular line.
Other settings could be anywhere from 01-
28, representing which day of the month the
test should be performed. Press the UP or
DOWN buttons to scroll through the days.
SUPV Report Prio:
[X] Account 1
AuxDis Alm/Supv Rpt.
[X] DISABLE
i
-Time Parameter-
1. AC-Loss Delay
2. Cellphone Date
3. Auto-Test Time
AC-Loss Delay(Hrs)
0
Cellular Report Date
0