Specifications
64
Configuration
Command Menu-->Dialer-Config
10.10.4 Time Parameters
Command Menu/Dialer-Config/Report 
Options
3. Supervisory priority
[X] Account 1->Default
[ ] Account 2
Use this function to set the account 
priority for reporting supervisory 
troubles. If the priority is set for 
account#1 then the dialer will try 
account#1 first for reporting.
Command Menu/Dialer-Config/Report 
Options
4. Aux Disc Alm/Supv Rpt.
[ ] ENABLE
[X] DISABLE ->Default
If this function is enabled, the Aux 
Disconnect feature (obtained by 
pressing the Aux Disconnect button) 
will block the alarm and supervisory 
events from being reported through the 
built-in dialer.
Note: Refer to 10.3 How to Use the Keypad to Program the FR-320 on page 49 for
detailed instructions on making menu selections. 
Command Menu/Dialer-Config/Time 
Parameter
1. AC Loss delay
0 ->Default
The AC loss delay 
ranges from 0 to 20 
hours
Use this function to delay the reporting of AC 
loss trouble on the dialer for the programmed 
time period. Press UP or DOWN button to 
increase or decrease the number of hours.
Command Menu/Dialer-Config/Time 
Parameter
2. Cellular report date
0 ->Default
The cellular report 
date ranges from 0 to 
28
Use this function to set the test report date 
for the cell phone setup. If the date is set to 
0, this means there is no test reporting for 
cell phone or the phone line is a regular line. 
Other settings could be anywhere from 01-
28, representing which day of the month the 
test should be performed. Press the UP or 
DOWN buttons to scroll through the days.
SUPV Report Prio:
[X] Account 1
AuxDis Alm/Supv Rpt.
[X] DISABLE
i
-Time Parameter-
1. AC-Loss Delay
2. Cellphone Date
3. Auto-Test Time
AC-Loss Delay(Hrs)
0
Cellular Report Date
0