Specifications

70
Pre-Programmed Modes
12.0 Pre-Programmed Modes
12.1 Mode 1: Agent Release, Single Hazard, Cross-zoned,
Combined Release
12.1.1 Zone Configuration
Detection Zone -1: Alarm (Hazard Area1, Cross-zoned)
Detection Zone -2: Alarm (Hazard Area1, Cross-zoned)
Detection Zone -3: Alarm (Pressure Switch or Water-flow)
Detection Zone -4: Supervisory (Non-latching by default)
Detection Zone -5: Abort Switch
Detection Zone -6: Manual Release Switch
NAC-1: Signal, will be on steady if there is any alarm zone or manual release switch
active.
NAC-2: Signal, indicates the cadence of hazard area 1 state or supervisory circuit
(optional).
RAC-1: Releasing Circuit (Hazard Area 1)
RAC-2: Releasing Circuit (Hazard Area 1)
12.1.2 Hazard Configuration
Default Release Timer Value: 60 seconds
Default Manual Release Delay: 0 seconds.
Default Abort Delay Type: Standard UL.
Default Soak Timer Value: 0 seconds
12.1.3 NAC Configuration
Default Escalating NAC code of Hazard Area State:
Hazard Idle: Off
Hazard Alert: Temporal
Detection Zones Phantom Zones Release Timers
Z1 Z2 Z3 Z4 Z5 Z6 Zp1 Zp2 RT1
Exp
RT2 Exp
Alm Alm WF Sup AB MR Z1+Z2 Z3+Z4
Out1 Signal Steady XXX X
Out2 Signal Escalating X(X) X X
Out3 Rel. Releasing XX
Out4 Rel. Releasing XX
RLS TMR 1 Started X
RLS Tmr 1 Interrupted X
RLS Tmr 1 Cancelled X
RLS Tmr 2 Started
RLS Tmr 2 Interrupted
RLS Tmr 2 Cancelled