Specifications
Module Settings
18
Jumpers for the Bell Cut Mode
JW2: Place jumper over pins 1 and 2 for the ability to remotely silence the bells on Zone 1.
JW3: Place jumper over pins 1 and 2 for the ability to remotely silence the bells on Zone 2.
JW4: Place jumper over pins 1 and 2 for the ability to remotely silence the bells on Zone 3.
JW5: Place jumper over pins 1 and 2 for the ability to remotely silence the bells on Zone 4.
J11: Wire these terminals to a bell cut relay (for details see QRM-1001 Bell Cut Module Installation and Operating
Instructions, LT-666).
Figure 14 Relay Adder Module (Model RM-1008A)
JW1: Remove continuity jumper if there are any more adder modules installed.
Jumper JW6 on the main fire alarm module must be removed if there are any adder modules installed.
The RM-1008A requires eight display points.
ATTENTION: Discard jumpers on zones that are not configured for bell cut.
Note: To have all relays work independently remove all jumpers off of their pins. To tie all commons
together, have all pins in place on their respective jumpers.
P1
P3
P4
FIELD WIRING TERMINALS
P2
JW1
Data cable to P5 of main
re alarm module or to
previous adder module
Data connector for next
adder module
Power connector to
P6 of main re alarm
module or to previous
adder module
Power connector for
next adder module
JP1
JP2
JP3
JP4
JP5
JP6
JP7
JP8