Specifications

System Configuration
42
Entering Configuration Mode
The system enters configuration mode whenever any of the configuration DIP switches 2 to 8 (switch 1 is used to
enter walk test mode) are set to a "1" or the ON position (top position). The Test / Config Mode and Common
Trouble LEDs will turn on and the buzzer will sound. You can silence the buzzer at this point.
If there is no activity (no buttons pressed or switches changed) for one hour, the system will return to normal
operation, but will remain in a trouble condition.
As you change the configuration DIP switches to select different functions, wait for a few seconds for the appropriate
LEDs to change as the system recognizes the change(s). Note that configuration changes take effect immediately
as they are made, there is no "undo" function.
Exiting Configuration Mode
To exit configuration mode after all desired changes are made, all configuration DIP switches must be returned to a
"0" or OFF position (bottom position). Wait about five seconds before pressing the System Reset button. The system
should now be back in normal operation.
0011 0011 33 Yellow Non-Silenceable Strobes
Relays
0011 1000 38 None Show Relay Circuits
Resize System
0100 0000 40 Yellow and Red Set Circuit Adder Module Number and Type
Correlations
0100 0001 41 Yellow Correlation by Input Circuit
0100 0010 42 Yellow Correlation by Output Circuit
Default
0111 1111 7F Yellow and Red Restore to Default Configuration
Walk Test
1000 0000 80 None Walk Test
Note: The fire alarm control panel is not operating as a fire alarm system while it is in configuration mode.
DIP Switch
Position
(1-8)
Function
Number
Button
Operations
Description