Advanced Life Safety Solutions Advanced Life Safety Solutions RA-1000 Series Remote Multiplex Annunciator Panels Canada 25 Interchange Way Vaughan, ON L4K 5W3 Tel: 905-660-4655 Fax: 905-660-4113 U.S.A. 42.20 Steve Reynolds Blvd, Unit 17 Norcross (Atlanta), GA 30093 Tel: 1-888-660-4655 Fax: 1-888-660-4113 © Mircom 2003 Printed in Canada Subject to change without prior notice www.mircom.com Installation and Wiring Manual LT-617 Rev.
RA-1000 Remote Annunciator Wiring and Instruction Manual Contents Introduction ............................................................................................................................. Technical Support ................................................................................................................ Installation Instructions.......................................................................................................... Wiring Instructions........................
Contents ii
RA-1000 Remote Annunciator Wiring and Instruction Manual Introduction Mircom's modular design RA-1000 Series Remote Multiplex Annunciator panels provide a large capacity of annunciation (up to 208 points) with Mircom’s standard FA-1000 Series Fire Alarm Control Panels. The RAM-1032(TZ) Main Annunciator Chassis is a 32-circuit annunciator that may be expanded with up to four RAX-1048(TZ) Adder Annunciator Chassis to a maximum of 208 circuit display points.
Installation Instructions Installation Instructions BACKBOX HEIGHT H MOUNTING A(IN.) MOUNTING B(IN.) BB-1001 9.0” 9.95” 7.5” BB-1002 18.0” 9.95” 16.5” BB-1003 26.5” 9.95” 24.9” BB-1008 33.0” 20.9” 35.2” BB-1012 45.0” 20.9” 52.0” BACKBOX WALL DOOR BACKBOX CAN BE MOUNTED WITH STANDARD 4" X 4" ELECTRICAL BOXES 12.75" B H A 1.
RA-1000 Remote Annunciator Wiring and Instruction Manual Wiring Instructions RS-485 WIRING The RS-485 wiring to the RAM1032(TZ) and RAM-1016(TZ) Module is recommended to be twisted shielded pair as shown in the diagram. The wire gauge may be: + 24 VDC INPUT 24 VDC POWER FROM FIRE ALARM CONTROL PANEL OR PREVIOUS ANNUNCIATOR + 24 VDC OUTPUT 24 VDC POWER TO NEXT ANNUNCIATOR - • 22 AWG up to 2000 ft. • 20 AWG up to 4000 ft.
DIP Switch Settings DIP Switch Settings Each annunciator assembly (main and adder chassis’) needs to be assigned a unique, sequential Address via the Main Chassis DIP Switch SW1. DIP Switch SW2 is used to allow disabling of some Front Panel push buttons (when individual switches are “ON” then the corresponding push button is disabled).
RA-1000 Remote Annunciator Wiring and Instruction Manual For FX-2000 Panels Set the annunciator “Address” (see the manual for the fire alarm control panel being used), as follows in the table below: Address SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 Address SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 33 ON OFF OFF OFF OFF 49 ON OFF OFF OFF ON 34 OFF ON OFF OFF OFF 50 OFF ON OFF OFF ON 35 ON ON OFF OFF OFF 51 ON ON OFF OFF ON 36 OFF OFF ON OFF OFF 52 OFF OFF ON OFF ON 37 ON
DIP Switch Settings On the RAX-1048(TZ) Adder Annunciator Chassis: P1: Connects to the Main Annunciator Chassis, or to the previous Adder Annunciator Chassis. P2: Connects to the Next Adder Annunciator Chassis. On the RAM-1032(TZ) Main Annunciator Chassis: P2: Connects to the first Adder Annunciator Chassis. P3,P11: Not used. Jumpers: Factory set. Do not change. P2 ADDER ANNUNCIATOR BOARD ;; ;; P1 P2 Terminals: See Wiring Instructions on page 3 for details.
RA-1000 Remote Annunciator Wiring and Instruction Manual Specifications and Features Enclosure Models BB-1001: Backbox for one annunciator chassis with keylock door. BB-1002: Backbox for up to two annunciator chassis with keylock door. BB-1003: Backbox for up to three annunciator chassis with keylock door. BB-1008: Backbox for up to eight annunciator chassis with keylock door. BB-1012: Backbox for up to twelve annunciator chassis with keylock door. Notes: 1. Enclosure finish: painted semi-gloss off white.
Specifications and Features RAX-1048(TZ) Adder Annunciator Chassis, 48 Display Points (TZ version has 48 extra trouble display points) • Interconnect via one ribbon cable to RAM-1032(TZ) or to previous RAX-1048(TZ). • Annunciation of up to 48 additional points (with trouble annunciation on the TZ version). • Standby: 15 mA Max., All LEDs “On”: 100 mA Max. • TZ version: Standby: 15mA Max., All LEDs “On”: 200mA Max.
RA-1000 Remote Annunciator Wiring and Instruction Manual Warranty & Warning Information Warning Please Read Carefully Note to End Users: This equipment is subject to terms and conditions of sale as follows: Note to Installers This warning contains vital information. As the only individual in contact with system users, it is your responsibility to bring each item in this warning to the attention of the users of this system.
Warranty & Warning Information Smoke detectors, heat detectors and other alarm initiating devices that are a part of this system may not properly detect a fire condition or signal the control panel to alert occupants of a fire condition for a number of reasons, such as: the smoke detectors or heat detector may have been improperly installed or positioned; smoke or heat may not be able to reach the alarm initiating device, such as when the fire is in a chimney, walls or roofs, or on the other side of closed
RA-1000 Remote Annunciator Wiring and Instruction Manual •Security and Insurance Regardless of its capabilities, an alarm system is not a substitute for property or life insurance. An alarm system also is not a substitute for property owners, renters, or other occupants to act prudently to prevent or minimize the harmful effects of an emergency situation. IMPORTANT NOTE: End-users of the system must take care to ensure that the system, batteries, telephone lines, etc.
Warranty & Warning Information Warranty Procedure To obtain service under this warranty, please return the item(s) in question to the point of purchase. All authorized distributors and dealers have a warranty program. Anyone returning goods to Mircom Technologies Ltd. must first obtain an authorization number. Mircom Technologies Ltd. will not accept any shipment whatsoever for which prior authorization has not been obtained.