Job Tree and Details Pane
5.1.2 Language
Specifies the language used to display system messages on the front LCD display and on any
LCD annunciator. User defined tags and messages will not be affected.
5.1.3 Options
Manual Signal Silence Check to enable the panel's Signal Silence switch.
Fire Drill Check to enable the panel's Fire Drill switch.
Waterflow Retard Operation if disabled, all the initiating circuits configured as waterflow act as
non-verified alarms. If enabled, retard operation is performed for
initiating circuits configured as waterflow
Auxiliary Disconnect Alarm
and Supervision
if enabled the auxiliary disconnect operation, disconnects alarm
and supervisory relays disabled the auxiliary disconnect operation
has no effect on the alarm and supervisory relays.
Alarm Transmit Silence this feature, if checked, causes the Alarm Transmit and Auxiliary
Alarm Relay to reset on Signal Silence rather than by the Reset
switch.
Common Supervisory Relay this feature, if checked, makes the common supervisory relay act
as a common alarm relay
Signal Isolator Used check this box if isolators are present on the loop 0 powered
output circuits.
Two Stage Operation check this box to configure the system as two stage, else it is
single stage.
Second Stage Alarm Relay
Operation
If enabled, the common alarm relay will be used for second stage
only of a two stage system. If disabled, it will be used for both
stages.
Positive Alarm Sequence check this box to enable the Positive Alarm Sequence feature. It
only applies to alarm input devices with the PA flag (F2) set. This
feature cannot be enabled if Two Stage Operation is enabled.
Monitor Alert check this box to have the panel produce alert sounds on monitor
in/out activation.
Polled Device Flashes check this box to cause device LEDs to flash when polled.