Job Tree and Details Pane
5.1.4 Timers
5.1.5 Date and Time
Class-A Loop check this box if the addressable loop on the base panel operates
in Class A mode.
Strobes Type Specify the Strobe Type that will be used on the panel.
• Gentex
• System Sensor
• Mircom
• Wheelock
Evacuation Code Specify the Evacuation Code that will be used on the panel.
• Continuous
• March Time
• Temporal
• California
Agency Selection Specify the Agency Standard that will be used on the panel.
• ULI Standard
• ULC Standard
Table 8 Timers
Timer Type Possible Settings
Signal Silence Inhibit Disabled, 10, 20, 30 seconds, 1 minute
Auto Signal Silence 5, 10, 15, 20, 25, 30 minutes
General Alarm Disabled, 5, 10, 15, 20, 25, 30 minutes
Power Fail Delay 0, 1, 2, 3 hours
Enable Daylight Savings Enable Daylight Savings.
Clock Daily Compensation Specify the number of seconds (signed) to be applied daily to the
panel clock.
Enable Auto After Hours Check this to enable after hours. Use the following controls to
configure after hours settings
Holidays - Modify Compose a new holiday definition in the YYYY MM DD edit boxes
and press Add holiday. You can specify recurring holiday by using
wild cards. For further instructions on adding/deleting holidays see
Chapter 5.1.6 Holidays.
Daytime Start and End
Hours
Specify when daytime begins and ends.
Weekend Start and End
Hours
Specify when the weekend begins and ends.