Installation manual
37
Job Tree and Details Pane
5.4 Bypass Groups
The list view displays the list of bypass groups currently defined in the system. You can
correlate any input or output device to a group, as well as a Led to indicate its status by
selecting Insert / Add Correlations from the main menu. The Led to be correlated must be
defined as "Bypass Zone" type on one of the RAX 1048TZDS display adders. Once a Led is
correlated to a bypass group, it will be used exclusively to indicate the status of that group and
it can not be used for other purposes.
Some columns containing advanced or internal information are normally hidden. They are
listed as Visible / No in the following table.
5.5 Hazard Zones
The Hazard Zone area displays any configured Hazard zones with the following information.
Table 11 Bypass Groups
Name Visible Description
No. Yes Group number of the bypass group
Tag Yes Label of the bypass group
No. Number of the Hazard Zone.
Zone Label Label of the Hazard Zone.
Type Configured as Pre-Action/Agent or Deluge.
Counting
Zone Type
Configured as Single, Double, Triple, 2 Input Type.
Abort Type Configured as ULI, IRI, NYC, AHJ.
Rel Delay The maximum value for the RDT is 60 seconds.
Soak Delay The maximum value for the SDT is 600 seconds.
Man Rel Delay The maximum value for the MRDT is 60 seconds.
Man Rel
Priority
To ensure a Manual Release Switch overrides an Abort Switch, in the FX-
3500 configuration software set the Man Rel Priority flag for the Hazard
Zone zone to Yes.