Installation manual
38
Job Tree and Details Pane
5.6 Main Display
This form view appears in the top, right pane when the Main Display item is selected in the Job
Tree view.
5.7 Display Adder
This list view appears in the top, right pane of the user interface when a display adder is
selected in the Job Tree. The list displays items (LEDs and Switches) of all the frames on the
selected Display Adder.
User Message. System Normal - specify the message to display on the front panel LCD
when the system is currently normal (no alarm or trouble).
Passcodes Level 1 - Not required
Level 2 and 3 - Specify the passcode for each level of access. Passcodes
must be numeric and a maximum of 20 digits long.
Access
Levels.
Specify the level of access for various front panel actions.
Level 1 does not require a passcode but a key to the panel is required
Level 2 is similar to Level 1 with additional access to disable zone
function, fire alarm devices, sensitivity, time and date settings
Level 3 has access to all functions
Table 12 Display Adder Info
Name Visible Description
Idx Yes Index - the zero based position of the item on the adder.
CPU No
The CPU Number of the Annunciator to which the adder is
attached.
Unnamed Yes
Linked Item - contains an asterisk if the item shares the same
LedGrp with other items. This means that correlations to one such
item are added to all linked items. Linked Items can be created
when Paste Special
is used. The linked items can be viewed with
the Linked Items
dialog.
Frame No
The Frame Number. An adder may contribute several frames to an
annunciator. The frame numbers are zero based.
LED No
The number (zero based) of the first LED of a logical group. For
example, an HOA adder has three LEDs per slide switch. This
column would show 0 for Idx 0, 3 for Idx 1, etc. Due to the way
some adders are arranged (hardware) the LED numbers are in
irregular sequences.
Sw No The Switch number (if any) associated with the Idx.
Type Yes
Initially this is the Type of display item. The values in the combo
box depend on the Adder/Frame type.
Assignment Yes Dependent on the Type.
F1 Yes
If the item is some form of switch (Bypass, Slide Switch) etc., then
this flag column can be set to ER (enable required) or none.