Installation manual

39
Job Tree and Details Pane
5.8 Dialer
This form is displayed when the Dialer tree item is selected. It allows you to configure the
UDACT / Dialer. The dialer can dial out on two phone lines. You must configure an account
and specify the line attributes for both. Line 2 can dial a cell phone. If this is the case the auto
test can be reduced from daily to monthly. The panel can also be configured from the
configuration tool by dialing in to the dialer. See Connect for full details.
5.8.1 Account 1
5.8.2 Account 2
5.8.3 Line 1
F2 Yes
For Bypass and Manual Switches, this flag can be set to AR (Aux
Reset Required). For Correlatable Switches it can contain NS (Non
silenceable)
F3 Yes
For Correlatable Switches this flag can contain GA (2nd stage, GA
device). For Bypass and Manual Push Switches it can contain SR
(System Reset Required)
F4 Yes
This flag prevents addressable device’s LED from flashing (and
activating the sounder when present). The LED flashes by default
and may only be changed to NO FLASH if the Authority Having
Jurisdiction allows.
Tag 1 Yes
Except for Common Controls, System Status and Man Ena, a 20
character tag can be entered. It will be used to identify the control
in messages, etc. For some Type/Assignment combinations the tag
is generated and cannot be edited.
Tag 2 Conditional
Correlatable Switches (being analogous to Input Zones) accept a
second line of 20 characters.
Account ID Six digit decimal for the SIA report formats and four digit hexadecimal for
Contact ID.
Telephone Text Field for telephone number.
Report Format Choose from SIA110, SIA300, Contact ID
Account ID Six digit decimal for the SIA report formats and four digit hexadecimal for
Contact ID.
Telephone Text Field for telephone number
Report Format Choose from SIA110, SIA300, Contact ID
Dial Using Tone/Pulse
Wait Check to wait for dial tone before dialling
Table 12 Display Adder Info
Name Visible Description