Job Tree and Details Pane
5.8.4 Line 2
5.8.5 Report Priority
5.8.6 Timers
5.8.7 Dialer
5.9 Common System Status
This list view appears in the top, right pane when the Common System Status item is selected
in the Job Tree.
System Statuses are pseudo inputs that can be correlated to outputs. For example:
Correlate a signal circuit to operate as a power supply. (using Init Done).
Customize the Fire Drill operation.
Correlate a relay to operate on Reset Command (using Sys Reset)
5.10 Input / Output Circuit Summary
The Job Tree always contains an Input Summary and Output Summary item. Select either of
these items to see a list of all of the circuits on the job.
Dial Using Tone/Pulse
Wait Check to wait for dial tone before dialling
Alarm Choose one of the two accounts to use to report Alarms
Supv Choose one of the two accounts to use to report Supervisory alerts
Trouble Choose one of the two accounts to use to report Troubles
AC loss delay 0-20 hours
Line 2 Cellular
Test
Check this box to indicate that Line 2 dials a cell phone. Use the Spin box
to specify the day of the month (1 - 28) for the cell phone test.
Auto test at Use this spin box to set the time for a daily test of land lines.
Line Retries Use this Spin Box to specify the number of retries to make (5-10)
Rings Use this Spin box to specify the number of rings when dialing in to
configure. Warning: if set to zero the next dial in session will not be able
to connect.
Mode Choose between DACT and UDACT
Enable Uncheck this box if you wish to set the dialer to the disabled state when
you send the job to the panel. If you receive a job from the panel when
the dialer was temporarily disabled then this check box will be un-
checked. The dialer is enabled by default.
Aux
disconnect
If enabled, the dialer will block the alarm and supervisory events from
being reported after the auxiliary disconnect button is pressed