Installation manual
45
Adding Items to the Job
To add a Display Adder
1. In the Job Tree select one of the listed annunciators and right click an item and select
Add Display Adder. The Add Display Adder window appears.
2. From the drop down menu select the desired Display Adder.
3. Click Add and the Display Adder will be added to the Job Details under the selected
Annunciator.
6.6 Deleting Correlations
If you change a Device Type, you might see the following message. This can happen after you
have performed an Auto Configuration on the panel.
Figure 32 Change process type warning
If you want to change the Device Type of a circuit that is correlated with a hazard zone, you
must delete the hazard zone from the correlations first.
To delete a correlation
1. Click the correlation, and then click the Edit menu and click Delete Item.
2. Click Yes to delete the correlation.
Hold down the Shift key to select more than one correlation at once.
6.7 Hazard Zones
Hazard zones can be added to FX-3500RCU panels. To determine if you have an FX-
3500RCU, go up to your panel, press Manual (M), and then press Information (?). If the letters
RCU are displayed at the end of the first line, your panel is an FX-3500RCU.
Hazard zones are configurable by correlating input devices, releasing circuits, (pre)release
signals, and manual release and abort switches. For more information on Releasing
Operation, see LT-1091 FX-3500RCU Releasing Application Guide. The URL for this guide
can be found in section 3.2 Related Documents on page 25.
Note: If you send a job with hazard zones to an FX-3500, the FX-3500 configuration
software will display an error message telling you that the panel is the wrong
model and that the job can only be sent to an FX-3500RCU panel.
Notes: Abort switches are only configurable in Preaction/Agent release applications.
Soak Delay timer is only configurable for Deluge applications.
i