Installation manual
46
Adding Items to the Job
6.7.1 Counting Zone Type
Releasing applications must be configured with one of the following Counting Zone types:
6.7.2 Abort Type
Releasing applications must be configured with one of the following Delay Timer types:
6.7.3 Configurable Timers
Releasing applications may be configured with the following timers:
Single Activation of any one input device correlated to the hazard zone will initiate
the release process.
Double Activation of any two input devices correlated to the hazard zone will confirm
the alarm and initiate the release process.
Triple Activation of any three input devices correlated to the hazard zone will
initiate the release process.
2 Input Types Activation of any two different input device types (ion, photo, heat etc.)
correlated to the hazard zone will initiate the release process.
ULI Press Abort and the timer continues to count down and stops and holds at 10 seconds.
Release the ABORT switch and the timer resumes the countdown at 10 seconds.
IRI Same as ULI with the following condition: For the Abort switch to function, you must press
and hold the Abort switch before the second zone goes into alarm.
NYC Pressing the Abort switch causes the control panel to add 90 seconds to the Release
Delay Timer (RDT).
Pressing and holding the Abort switch stops the Release Delay Timer (RDT) from
counting down. Releasing the Abort switch resumes the count down of the RDT.
AHJ The timer does not start while you press and hold the Abort switch. Press the Abort switch
and the timer resumes counting down. Press the Abort switch again to restore the timer to
its full value. Release the Abort switch and the timer resumes counting down.
Release Delay Timer
(RDT)
The amount of time from when the Hazard Zone is activated
via correlated input devices until release.
The maximum value for the RDT is 60 seconds.
Soak Delay Timer
(SDT)
The amount of time that the releasing circuit will be active.
Upon the expiration of Soak Timer, the releasing circuits will
be shut off. Only configurable in Deluge applications.
The maximum value for the SDT is 600 seconds.
Configuring the SDT to 0 seconds causes the releasing
circuits to shut off ONLY when the system is reset.
Manual Release Delay Timer
(MRDT)
The amount of time from when the Manual Release Switch is
pressed until release.
The maximum value for the MRDT is 60 seconds.