Adding Items to the Job
To add a Hazard Zone
1. From the Job Tree select Hazard Zone.
2. Right click in the Details Pane and select Add Zone. A zone will now be added to the
Details Pane.
3. Enter the following Information
Attention: Manual Release cannot be aborted once it has been initiated.
Zone Label Name of the Zone
Type Pre-Action/Agent or Deluge
Counting Zone Type Single, Double, Triple, 2 Input Type
Abort Type ULI, IRI, NYC, AHJ
Rel Delay The maximum value for the RDT is 60 seconds.
Soak Delay The maximum value for the SDT is 600 seconds.
Man Release Delay The maximum value for the MRDT is 60 seconds.
Manual Release Priority To ensure a Manual Release Switch overrides an
Abort Switch, in the FX-3500 configuration software
set the Man Rel Priority flag for the Hazard Zone
zone to Yes.
!