Battery Capacity Requirement
Battery (AH) = (Standby Current Total x Discharge Time) + (Alarm Current Total x Alarm Time)
([STANDBY (A) ______ ] X [(24 Hours) ___ ]) + ([ALARM (B) ______ ] X [Alarm in Hr.] _____) = (C) ______AH
Total Alarm Current must be 10 amperes or less. NAC Circuits must not exceed 6 amperes.
Battery Selection
Battery Size = Multiply (C) by 1.20 to derate battery.
See the following table for the recommended Mircom batteries for use with this panel
BA-110 (12 AH) and BA-117 (18 AH) will fit into the BBX-1024DS.
To house BA-124 (26 AH) and BA-140 (42AH) batteries a BC-160 Battery Cabinet is required.
Use of alternative batteries may result in failure of the panel to meet agency and regulatory requirements, and may result in
shortened battery life. Batteries should be tested regularly, and replaced at least every three years. If the Battery Trouble
indicator activates, obtain required service.
MIX-
M501DMAP(A)
Advanced Protocol Dual
Input Mini Monitor Module
(ULC)
X ==
MIX-M501MAP(A)
Advanced Protocol Mini
Monitor Module (ULC)
X .0004 = .0020 =
MIX-M502MAP(A)
Advanced Protocol
Conventional Zone Module
(ULC)
X .0004 = .0052 =
B501BH(A)
Intelligent Sounder Base
(ULC)
X .001 = .015 =
B501BHT(A)
Intelligent Temporal Tone
Sounder Base (ULC)
X .001 = .015 =
INX-10A Main Chassis (10 Amp) X 0.0045 = 0.0045 =
Device & Remote LEDs (Maximum 20 per loop) X =
Signal Load (bells, horns, strobes, and etc.) X =
Auxiliary Power Supply (Aux 1, Aux 2, Un-filtered) =
Alarm
=
Total currents (Add above currents) STANDBY (A)(B)
Table 45 Recommended Batteries
Battery Model Battery Size UL/ULC Rating
BA-110 12AH 10AH
BA-117 18AH 17AH
BA-124 26AH 24AH
BA-140 42AH 40AH