Specifications

Installation Manual is LT-1083
OPERATING INSTRUCTIONS
Normal: Indicators are O except for green A.C. light. FACP shows trouble after power-up until “system reset” pressed. Alarm: Flashes red when alarm in queue. Buzzer sounds steady. Once all alarms reviewed LED
illuminates steady. Resetting panel clears indication and turns LED o. Supervisory: Flashes yellow at Fast Flash Rate when Latching or Non-Latching Supervisory circuit activated. Buzzer sounds at fast rate. Pressing
button cycles list of active supervisory alarms from oldest to newest. Once all alarms are reviewed LED illuminates steady. If all Non-Latching Supervisory circuits are restored and no Latching Supervisory Circuits are active,
indication clears and LED turns o. Resetting panel clears activation of any Latching Supervisory Alarms, clears indication and turns LED o. Trouble: Flashes yellow when any trouble condition is detected. Buzzer sounds
at slow rate. Pressing button cycles list of active supervisory alarms from oldest to newest. Once all troubles in queue are reviewed LED illuminates steady. Clearing all Trouble conditions clears indication and turns LED o.
Monitor: Flashes yellow at Trouble Flash rate when any Monitor condition is detected. Buzzer sounds at fast rate. Pressing button cycles through a list of active Monitor Conditions from oldest to newest. Once all conditions
in the queue have been reviewed LED illuminates steady. Clearing all Monitor conditions clears indication and turns LED o. System Reset: System Reset button resets FACP and all Circuits. Pressing System Reset button
causes a trouble to occur and LED illuminates steady yellow. Resetting System clears indication and turns LED o. Acknowledge - Two Stage and PAS Only: Flashes yellow at Fast Flash Rate as Auto General Alarm Timer
is timing. Illuminates steady yellow by pressing Acknowledge or Signal Silence
buttons and cancelling the Auto General Alarm Timer. Expiring of Auto General Alarm Timer causes Panel to enter General Alarm, clears indication and turns LED on. For Positive Alarm Sequence (PAS) the Acknowledge
button must be pressed within 15 seconds of the signal, refer to section 5.8 in LT-1083. General Alarm: LED illuminates steady red when General Alarm button is pressed, a General Alarm Initiating Circuit activates or Auto
General Alarm Timer expires. Resetting System clears indication and turns LED o. Signal Silence: Flashes yellow at Trouble Flash rate when Indication Circuits are silenced. Any Subsequent Alarms cause Signals to
resound, clears indication and turns LED o. Pressing Signal Silence button when Panel is in Alarm turns on Signal Silence Indicator and deactivates any Silenceable Indicating Circuits. Non-Silenceable Circuits are
unaected. Signals re-sound upon any subsequent Alarm. Additional Two Stage Function: If the Auto General Alarm Timer has not expired, Signal Silence button also performs same function as Alarm Acknowledge
button. Buzzer Silence: Flashes yellow at Trouble Flash rate when Buzzer Silence button is pressed. Any new alarm, supervisory or trouble events resounds buzzer and causes LED to turn o. Visual Indicator Test: Press
and holding the Visual Indicator Test button illuminates all front panel LEDs on steady and turns the buzzer on steady. If Visual Indicator Test is active for more than 10 seconds, Common Trouble activateds. Fire Drill:
Illuminates steady yellow during active Fire Drill. Pressing Fire Drill button activates all programmed and non-Disconnected Indicating Circuits. Does not transmit any Alarms via City Tie, or Common Alarm Relay. Fire Drill
may be programmed to operate specic Indicating Circuits. Fire Drill is cancelled by pressing the button again (toggle switch), or if Panel goes into a real Alarm. Note: Test all indicators regularly.
SYSTEM LIMITATIONS: DO NOT EXCEED POWER SUPPLY RATINGS, ALL CIRCUITS ARE SUPERVISED AND POWER LIMITED WHERE APPLICABLE
NAC Circuits: 4 supervised style Y (Class B) indicating circuits, congured as strobes or audibles. Terminals are labelled as “NAC 1”, “NAC 2”, “NAC 3” and
“NAC 4”. Rating Power limited / Regulated 24V FWR / 1.5A @ 49C per circuit. Max NAC power allowed 6.0A (1.5A max per circuit). Total Max power 10A.
Addressable Loops: Terminals are labelled “Loop A” and “Loop B” on Main Board. Power Limited 22VDC/350mA, for wiring info refer to manual.
Aux Supply: Terminals are labelled as “AUX 1”. Power limited / 24VDCregulated / 500mA max.
Resettable Aux Supply: Terminals are labelled as “AUX 2”. Power limited / 24VDC regulated / 300mA max.
Unltered Supply: Terminals are labelled as “Special Application” 24V FWR/1.7A max
RS-485 Interface: Terminals are labelled “RS-485”. Power Limited 300mA
Polarity Reversal: Terminals are labelled “POLARITY REVERSAL” on PR-300. Power Limited / 24VDC open / 12VDC at 3.5mA / 8mA max(shorted)
City Tie: Terminals are labelled “CITY TIE” on PR-300. Power Limited / 24VDC unltered / 250mA max/13.7 or 14.4 ohm trip coil
BATTERY MAINTENANCE:The two 12 VDC sealed lead-acid batteries should be replaced after each period of 3 to 5 years of normal service. If the Battery Trouble indicator activates,
obtain required service.
NP-7329 Rev.1 June 2013
SYSTEM CONFIGURATION
Electrical Ratings 120VAC 60Hz/240VAC 50Hz, 10A slow blow fuse on
secondary of transformer
Battery Fuse: 20A slow blow micro fuse built into WX-058 battery cable,
eld replaceable
Signal Silence Inhibit:
_ None _ 1 _ 2 _ 3 minutes
Automatic Sig Silence Period:
_ None _ 5 _ 10 _15
_ 20 _ 30
Manual Signal Silence:
_ No(disabled) _ 5 _ 10 _ 15
_ 20 _ 30 minutes
City Tie:
Disconnectable
_ No _ Yes
Stage Select:
_ Single Stage _ Two Stage _ Positive Alarm Sequence
Waterow:
_ No _ Yes Zone # ____________
Pre-alert Period (Two Stage):
_ None _ 5 _ 10 _ 15
_ 20 _ 30 minutes
Power Supply: _ 10A maximum
Smoke Detector
Circuit (Zone)
Control Unit Delay
Seconds
Model Delay, Seconds (1)
1) Enter Detector Data here; the delay (power-up) (start-up) time marked on the installed Smoke
Detector(s), or on their installation wiring diagram(s) is to be used.
Use of Product – “Commercial” and “Protected Premise Control Unit”
WARNING: THIS UNIT INCLUDES AN ALARM VERIFICATION FEATURE THAT WILL RESULT IN A DELAY OF THE SYSTEM ALARM
SIGNAL FROM THE INDICATED CIRCUITS. THE TOTAL DELAY (CONTROL UNIT PLUS SMOKE DETECTORS) SHALL NOT
EXCEED 60 SECONDS. NO OTHER SMOKE DETECTOR SHALL BE CONNECTED TO THESE CIRCUITS UNLESS APPROVED BY
THE LOCAL AUTHORITY HAVING JURISDICTION.
Local Service Representative
Name: ________________________________________
Company: ________________________________________
Address: ________________________________________
Telephone: ________________________________________
System Model: FX-3500 Fire Alarm Control Panel
System Type: Local, Auxiliary (using PR-300), Remote Station (using PR-300), Central Station
Type of Service: A, M, WF, SS
Type of Signaling: Non-Coded, Marching Time
Applicable Standards: NFPA 70, 72, 12, 12A, 12B, 13,15, 16, 2001, CAN/ULC-S559-04,
UL-864 Rev. 9, ULC S524, CAN/ULC-S527-11 and ULC-S536-04
Installation Environment: Indoor use only/ dry environment
Manufactured in Canada by: Mircom Technologies Limited
25 Interchange Way, Vaughan,L4K 5W3
Ontario, Canada
Tel:(905)660-4655, Fax:(905)660-4113
AVERTISSEMENT: CE POSTE EST MUNI D’UNE FONCTION DE VÉRIFICATION D’ALARME QUI ENTRAÎNERA UN RETARD DU
SIGNAL D’ALARME DU SYSTÈME DANS LES CIRCUITS INDIQUÉS. LE RETARD TOTAL (POSTE DE CONTRÔLE PLUS LES
DÉTECTEURS DE FUMÉE) NE DOIT PAS DÉPASSER 60 SECONDES. AUCUN AUTRE DÉTECTEUR DE FUMÉE NE DOIT ÊTRE
RELIÉ À CES CIRCUITS (ZONES) SAUF SUR APPROBATION DE L’AUTOITÉ COMPÉTENTE LOCALE.
WARNING: RADIO FREQUENCY FROM TRANSMITTING DEVICES MAY IMPAIR INTENDED OPERATION OF THE CONTROL UNIT.
MAINTAIN A MINIMUM OF 30 CM BETWEEN TRANSMITTING DEVICES AND CONTROL UNIT.
AVERTISSEMENT : LES RADIOFRÉQUENCES ÉMISES PAR LES DISPOSITIFS DE TRANSMISSION PEUVENT NUIRE AU
FONCTIONNEMENT PRÉVU DU POSTE DE CONTRÔLE. MAINTENIR UNE DISTANCE D’AU MOINS 30 CM ENTRE LES
DISPOSITIFS DE TRANSMISSION ET LE POSTE DE CONTRÔLE.
Instructions are to be framed and placed adjacent
to the control unit for ready reference