Specifications
27
Installation
Table 9 Main Board Connectors and Jumper
Connector/
Jumper
Description
P2 To Power Supply
P3 To Power Supply
P4 Ribbon Cable connects to P4 of MAM-3500
P5 To PC Configurator
P8 To PR-300
P9 To Printer
P10 To ALC-636 Loop Adder
P11 Factory Use Only
P13 USB Port
P14 Future Use
JW1 Must be ON - Allows Configuration Connection
JW2 Must be ON - Annunciator End of Line
JW5 Normally open. Place jumper here and power down (AC and batteries) and power
back to restore Master Password. After reset, remove jumper and leave normally
open.
JW6 Normally open to BLOCK remote configuration via modem. Place jumper here to
ALLOW for remote configuration. When jumper is set panel will indicate a trouble.
JW7 On the Main Fire Alarm Module, this jumper must be removed if a PR-300 Polarity
Reversal and City Tie Module is installed.
JW10 Must be in the 1-2 Position (Bottom 2 Pins) - Allows PC Connection through serial port
JW11 Place in the 1-2 Position (Bottom 2 Pins) for Serial Port or Place in the 2-3 Position
(Top 2 Pins) for Keltron Dialer
JW12 If set will output debug trace in the RS-232 port. Normally should not be used.
Attention: ADVANCED INSTALLER NOTE
Setting JW5 and JW6 at start-up will revert the panel to the default
configuration.
!