4.3.1 Installing the PR-300 Polarity Reversal and City Tie Module
Mount the PR-300 as shown in Figure 5.
The Alarm Transmit signal to the PR-300 can be programmed to turn OFF when signal silence
is active. This allows the City Tie Box to be manually reset. On subsequent alarms the
silenceable signals will resound and the City Tie Box will be retriggered.
The Trouble Transmit signal to the PR-300 can be programmed to delay AC power fail 0, 1, 2,
or 3 hours if this is the only system trouble.
Figure 5 Installing the PR-300 Polarity Reversal and City Tie Module
4.4 Installing the ALC-636 Dual Loop Adder
Mount the ALC-636 Dual Loop Adder as shown in Figure 5.
The panel can provide up to 350mA of alarm current to the devices on the loop. For device
currents see Appendix F - Battery Calculations on page 100.
Table 10 PR-300 Polarity Reversal and City Tie Module Connectors and Jumpers
Item Setting
P1 Connect cable to P8 on the Main Board of the FX-3500
JW4 Not used. Keep jumper intact.
Note: If using a PR-300 remember to remove JW7 on the main board. For the location
of JW7 on the main board see Figure 3.