5.5 Single Stage Operation
In a single stage system, all alarm inputs are treated in a similar manner. Alarm inputs include
any of the following:
Non-verified alarm
Verified alarm
Waterflow alarm
Sprinkler alarm
Any of the above alarm inputs activating when the panel is not already in alarm cause the
following:
The buzzer sounds steady.
Cancels active fire drill.
Common Alarm LED turns ON.
Common Alarm relay activates if Aux disconnect is not active.
The Auto Signal Silence timer activates (if configured).
The Signal Silence Inhibit timer activates (if configured).
If Aux disconnect is not active, activates all non-disconnected indicating circuits
programmed to the input.
Activates non-disconnected strobes associated with the input.
Activates non-disconnected signals associated with the input at the evacuation rate.
Subsequent alarms when the panel is already in alarm, cause the following:
The alert buzzer sounds steady.
Resounds silenced signals, turns off the Signal Silence LED, and restarts the Auto
Signal Silence timer (if configured).
Activates continuously any additional non-disconnected strobes associated with the
input.
Activates at the evacuation rate any additional non-disconnected signals associated
with the new input.
5.6 Two-Stage Operation
In a two stage system, alarm inputs are either first stage (alert) inputs or second stage
(general alarm) inputs. First stage inputs include inputs from the following types of circuits:
Non-verified alarm
Verified alarm
Sprinkler alarm
Water-flow alarm
Second stage inputs include the following:
Alarms on the general alarm inputs.
Activation of the General Alarm button.
Expiration of the Auto General Alarm timer.
Any of the above alarm inputs activating when the panel is not already in alarm cause the
following:
The buzzer sounds steady.