Specifications
67
Wiring
7.1.4 Input Circuits
If using conventional input circuits in an FX-3500 system MIX-502MAP(A), MIX-502M and
CZ-6 Conventional Zone Modules must be used.
1.20 118 36 185 56 300 91 425 129 1.5
1.50 94 29 150 46 240 73 343 105 1.2
1.70 78 24 125 38 200 61 285 87 1.0
Notes: Main Board NAC Circuits are rated for of 1.5 Amperes each.
Maximum Voltage Drop Should Not Exceed 1.67 Volts
Table 21 MIX-502MAP(A) Conventional Zone Module Input Circuit Wiring Table
Wire Gauge Maximum Wiring Run to Last Device and Back (ELR)
(AWG) ft m
18 3787 1154
16 5952 1814
14 9615 2930
Notes: Maximum Loop Resistance Should Not Exceed 25 Ohms.
Maximum Wiring Run indicates wiring distance out and back to the panel. The
resistance accross the shorted wire should be less than 25 Ohms.
Table 20 NAC and Auxiliary Power Circuits Wiring Table
TOTAL
SIGNAL
LOAD
MAXIMUM WIRING RUN TO LAST DEVICE (ELR) MAX. LOOP
RESISTANCE
18AWG 16AWG 14AWG 12AWG
i
i