Specifications

75
Wiring
7.5.3 PR-300 Polarity Reversal and City Tie Module Wiring
Wire the PR-300 Polarity Reversal and City Tie Module successfully as shown in Figure 21.
Plug PR-300 ribbon cable P1 into connector P8 on the Main Fire Alarm Board.
Remove jumper plug from JW7 on the Main Fire Alarm Board.
Power Limited cable type FPL, FPLR or FPLP must be used.
For USA installation, the installer must use Atlantic Scientific (Tel: 407-725-8000), Model
#24544 Protective Device, or similar UL-Listed QVRG secondary protector, as shown.
For installations in Canada, the Protective Device is not required but still recommended.
Figure 21 Wiring the PR-300 Polarity Reversal and City Tie Module
1
2
s
1
2
s
1
2
s
1
2
s
CITY TIE LOCAL ENERGY
RATED - 24VDC FILTERED
TRIP COIL - 13.7 and 14.4 Ohms,
270mA, 5mV RIPPLE
PROTECTOR
UNPROTECTED
PROTECTED
POLARITY REVERSAL ALARM
24VDC OPEN
12VDC AT 3.5mA
8mA MAX. SHORT
POWER LIMITED
POWER LIMITED
+
-
+
-
+
-
POLARITY REVERSAL SUPV.
24VDC OPEN
12VDC AT 3.5mA
8mA MAX. SHORT
POWER LIMITED
+
-
USE A SHORTING WIRE
WHEN THE CITY TIE IS
NOT USED
DIN RAIL CONNECTION
TO EARTH GROUND
+
-
1
2
s
1
2
s
1
2
s
1
2
s
PROTECTOR
UNPROTECTED
PROTECTED
+
-
DIN RAIL CONNECTION
TO EARTH GROUND
CONFIRMS TO NEMA STANDARD SB3-1969
INTENDED FOR CONNECTION TO POL
REVERSAL CIRCUIT OF A REMOTE
STATION RECEIVING UNIT HAVING
COMPATIBLE RATINGS