Specifications

99
12.2 FX-3500 System Module and Annunciator Specifications
Aux supply 2 Power limited / 24VDC regulated / 300mA max
Unfiltered supply Power limited / 24V FWR special application / 1.7A max at 49C
List of Compatible Devices: RAM-1016TZDS, RAM-1032TZDS, RAM-3500-LCD,
RAX-LCD-LITE
Auxiliary relays Common Alarm/
Supv./Trouble/
Auxiliary Alarm
Must be connected to a listed power limited source of
supply Form C/28VDC/1A max
RS-485 port For remote annunciators. Terminals are labelled “RS-485”.
Ground Fault
Impedance
10 K Ohms
Open Circuit Fault 100 K Ohms
Short Circuit Fault 0 Ohms
Table 44 FX-3500 System Modules and Annunciator Specifications
FX-3500 System Modules and Annunciators
RAM-
3500LCD
Remote Annunciator Standby 70mA / alarm 100mA
RAX-LCD-
LITE
Remote Annunciator Standby 65mA / alarm 80mA
RTI-1 Remote Trouble Indicator Normal standby 0mA / alarm 30mA maximum
PR-300 Polarity Reversal and City Tie Module
City Tie power limited / 24VDC unfiltered / 270mA max / 13.7 and
14.4 Ohms
Polarity Reversal power limited / 24VDC open / 12VDC at 3.5mA / 8mA
max (shorted)
Polarity Reversal Supv.
Terminal
24VDC (normal) / -24VDC (supervisory) / 0V (trouble)
Polarity Reversal Alarm
Terminal
24VDC (normal) / -24VDC (alarm) / 0V (trouble)
Current Consumption standby 50mA / alarm 300mA (city tie in use) / alarm
70mA (city tie not in use)
Table 43 FX-3500 Specifications (Continued)
FX-3500 Series Fire Alarm Control Panel