Specifications

11
Introduction
Enable or disable the Battery Charger on activation
Class A or B output signals
Horn/Strobe sync protocols include Mircom, Amseco, Gentex, System Sensor and
Wheelock
Ability to sync outputs for multiple INX-10A units
2 wire horn/strobe Sync mode allows audible notification appliances (horns) to be
silenced while visual notification appliances (strobes) continue to operate
Audible signals may be configured for Steady, Temporal Code, California Code and
March Time
Output fault notification to FACP
Built-in charger for sealed lead acid or gel type batteries
Enclosure fits 4AH, 7AH and 12AH batteries
2.5 Amp max current per output
1.7 Amp auxiliary power output
Unit includes power supply and charger, red enclosure, cam lock, transformer and
battery leads
Compatible with 24VDC fire panels
Surface or flush-mountable
1.1.3 General Notes
Circuits And Zones
Circuits refers to an actual electrical interface, Input (Detection), NAC Notification Appliance
Circuit) which connect audible and visible notification appliances to the fire alarm system
control unit (Signal), or Relay.
Wiring Styles
Input Circuits are configured as Class B (Style B).
NAC Circuits may be individually wired as Class A (Style Z) or Class B (Style Y) without
affecting the number of circuits available.
Signal Line Circuit Class A (Style 7) and Class B (Style 3).