Specifications
23
Indication & Controls
Ground Fault Trouble
Flashes amber when there is a ground fault trouble. To correct the fault, check for any external
wiring touching the chassis. Jumper, a wire loop, must be installed to enable Ground Fault
detection. For wiring information see Figure 37 Relay, Ground Supervision and Auxiliary
Supply Wiring on page 74. For configuration information see 6.2.2 Setting Protocols,
Reporting, Charger, Battery Installed on page 34.
4.1.3 Other LEDs
Figure 8 Additional LEDs
Addressable (SLC) Loop Indicators
Three LEDs. Two LED’s that flash green for incoming activity for each loop, and one that
flashes red for outgoing loop activity.
Synchronized Input Indicators
Two LEDs. One LED on each input that flashes green for incoming activity.
Trouble Relay Indicator
One LED that is steady green for system OK.
Alarm Relay Indicator
One red LED that is steady red when an alarm is activated.
NAC Circuit Indicators
Each NAC Circuit has one red LED that flashes when activated and one amber that activates
solid when a trouble occurs. To clear the trouble and reset the panel press the acknowledge
button.
Synchronized Output Indicators
Two LEDs. One LED on each output that flashes green for outgoing activity.
4.1.4 Flash Rate
Trouble Flash
20 flashes per minute, 50% duty cycle.
4.1.5 Controls
Acknowledge Button
This button is used to clear any trouble indications on the INX-10A.
Configuration DIP switches
The DIP switches are used for a variety of different configuration settings. For more
information see Chapter 6.0 Configuration on page 30.
-
+ +
-
ADDRESSABLE LOOP
-
+ +
-
SYNCH. INPUT 1
-
+ +
-
SYNCH. INPUT 2 TROUBLE RELAY ALARM RELAY
NC NO C
ALARM RELAY
NC NO C
NAC 1
YZ
+
Z
+
Z
-
YZ
-
NAC 5
YZ
+
Z
+
Z
-
YZ
-
NAC 4
YZ
+
Z
+
Z
-
YZ
-
NAC 3
YZ
+
Z
+
Z
-
YZ
-
NAC 2
YZ
+
Z
+
Z
-
YZ
-
-
+ +
-
SYNCH OUTPUTS
12
INPUT
ACTIVE
INPUT
ACTIVE
SYSTEM
OK
ALARM
OK
NAC ON TROUBLE NAC ON TROUBLE NAC ON TROUBLE NAC ON TROUBLE NAC ON TROUBLE
RECV1
RECV2 XMIT
C
P
NC
NO