Specifications
25
Operation
5.1 Circuit Types
Any failure on the SLC loop activates any configured NAC Circuits.
5.1.1 NAC (Output) Circuits Types
Signal
For audible devices such as bells and piezo mini-horns. While sounding, these follow the
pattern appropriate for the condition;
• the configured Evacuation Code (default is Temporal Code) during Single-Stage Alarm
• Two-Stage General Alarm
• or the Alert Code during Two-Stage’s Alert (First) Stage.
Strobe
For visual devices such as strobes that use no code pattern (they are continuous) and follow
input contact.
Synchronized Strobes
For visual devices such as strobes that support Mircom/Amseco, System Sensor, Gentex,
Wheelock proprietary code patterns, configure to the appropriate pattern.
DC Power Supply
Uses no code pattern (they are continuous) and cannot be silenced. Configured via DIP
switches and is not allocated an SLC address.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for
Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific
values or not used at all as indicated below.
Program feature or option Permitted in UL 864? (Y/N) Possible settings
Settings permitted in UL
864
Second Stage Enabled YES
Second Stage Enabled/Disabled
(Free loop addresses base +7 to base
+11)
Second Stage Enabled
AC Trouble YES
Return Specific ULC Trouble/Free
loop addresses base +2 to base +4
Reporting of ULC Specific
trouble is permitted
Battery/Charger Trouble YES
Return Specific ULC Trouble/Free
loop addresses base +2 to base +4
Reporting of ULC Specific
trouble is permitted
Ground Fault YES
Return Specific ULC Trouble/Free
loop addresses base +2 to base +4
Reporting of ULC Specific
trouble is permitted
Attention: If the INX-10A has configured NAC circuits the Evacuation Rate or Strobe
Rate MUST be set via the appropriate DIP switches or a trouble will sound.
For more information see 6.2.3 Charger Settings, Synchronization Settings,
NAC Input Settings on page 35 and 6.2.4 Setting Alert Rates, Evacuation
Rates, NAC 5 Output Functions on page 36.
!