Specifications

37
Configuration
6.2.5 Setting Strobe Types, NAC 1-3 Supply Settings, NAC 4 Output Function
Use DIP switch 5 to configure Strobe types, NAC 1-3 settings and NAC 4 output functions.
Table 9 Setting Strobe Types, NAC 1-3 Supply Settings, NAC 4 Output Function
DIP switch 5 Switch #
Default Setting = 0 Activated Setting = 1
Notes/
Additional
Diagrams
1-3 Setting Strobe Manufacturer
1-3
000 - Disable
If the INX-10A has NAC circuits configured the
Evacuation Rate or Strobe Rate MUST be enabled or a
trouble will sound.
1-3 100 - Mircom/Amseco
1-3 010 - Not Used
1-3 110 - System Sensor
1-3 001 - Secutron/Gentex
1-3 101 - Wheelock
4 NAC 1 - NAC NAC 1 - Continuous Supply
5 NAC 2 - NAC NAC 2 - Continuous Supply
6 NAC 3 - NAC NAC 3 - Continuous Supply
7-8 NAC 4 Output Settings
7-8 00 - NAC
7-8 10 - Continuous Supply
7-8 01 - Cut on Alarm
7-8 11 - 2 seconds Cut on Reset
ALL SWITCHES OFF