Specifications

41
Configuration
6.3.2 Single Stage with Enhanced Trouble Reporting Addressing
To configure the recommended base address
To configure the INX for Single Stage with Enhanced Trouble Reporting in a Mircom
System
To configure the INX for Single Stage with Enhanced Trouble Reporting in a Secutron
System
Set DIP switch SW1 as: 0-1-0-1-1-0-1-0
OFF-ON-OFF-ON-ON-OFF-ON-OFF
Set DIP switch SW2-1 to SW2-4 as: 0-0-0-1
OFF-OFF-OFF-ON
Set DIP switch SW2-1 to SW2-4 as: 0-1-0-1
OFF-ON-OFF-ON
Table 11 Configuring Single Stage with Enhanced Reporting Functions
Function Address Recommended
Address
Common Trouble Base Address 190
Signal Silence Base Address + 1 191
Monitor AC trouble Base Address + 2 192
Monitor Battery/Charger trouble Base Address + 3 193
Monitor Earth Ground Fault Base Address + 4 194
Activate NAC1, return NAC1 line status Base Address + 5 195
Activate NAC2, return NAC2 line status Base Address + 6 196
Activate NAC3, return NAC3 line status Base Address + 7 197
Activate NAC4, return NAC4 line status Base Address + 8 198
Activate NAC5, return NAC5 line status Base Address + 9 199
Notes: Table 11 represents all NACs configured as NAC circuits.
Mircom recommends always using the upper range of addresses available for
the INX-10A.
If any NAC circuit is configured as a Power Supply see 6.3.4 Single Stage with
Enhanced Reporting and Power Supply Output Addressing for an explanation on
addressing.