Specifications
43
Configuration
6.3.3 Single Stage with Basic Reporting and Power Supply Output Addressing
In order to maximize the amount of addresses available, if a NAC circuit is configured as a
Power Supply, the next configured NAC Circuit is assigned the address reserved for the
previous Circuit.
Example Application
• NAC 5 configured as a Power Supply.
• INX-10A Common Trouble reporting address is 194.
To configure the recommended base address
To configure the INX for Single Stage with Basic Reporting in a Mircom System
To configure the INX for Single Stage with Basic Reporting in a Secutron System
To configure NAC 5 as a Continuous Power Supply
Set DIP switch SW1 as: 0-1-1-1-1-0-1-0
OFF-ON-ON-ON-ON-OFF-ON-OFF
Set DIP switch SW2-1 to SW2-4 as: 0-0-1-1
OFF-OFF-ON-ON
Set DIP switch SW2-1 to SW2-4 as: 0-1-0-1
OFF-ON-OFF-ON
Set DIP switch SW4-7 and SW4-8 as: 1-0
ON-OFF
Table 12 Assigning Addresses - Single Stage with Basic Reporting and Power Supply
Output
Function Address Recommended
Address
Common Trouble Base Address 194
Signal Silence Base Address + 1 195
Activate NAC1, return NAC1 line status Base Address + 2 196
Activate NAC2, return NAC2 line status Base Address + 3 197
Activate NAC3, return NAC3 line status Base Address + 4 198
Activate NAC4, return NAC4 line status Base Address + 5 199