Configuration
Figure 18 FX-2000 Configurator Settings - INX-10A Single Stage with Enhanced
Reporting and Power Supply Output
Table 13 Assigning Addresses - Single Stage Application, 1 Power Supply Output
Function Address Recommended
Address
Common Trouble Base Address 191
Signal Silence Base Address + 1 192
Monitor AC trouble Base Address + 2 193
Monitor Battery/Charger trouble Base Address + 3 194
Monitor Earth Ground Fault Base Address + 4 195
Activate NAC1, return NAC1 line status Base Address + 5 196
Activate NAC2, return NAC2 line status Base Address + 6 197
Activate NAC3, return NAC3 line status Base Address + 7 198
Activate NAC4, return NAC4 line status Base Address + 8 199
Notes: Mircom recommends always using the upper range of addresses available for
the INX-10A.
Mircom recommends always using the upper range of NACs (NAC5 then NAC4
then NAC3 etc.) when configuring as a Power Supply.