Specifications

48
Configuration
6.4 Two Stage Addressing Options
Address Assignments are done via DIP switch 2(SW2) which is located to the left of the Main
LED display board. The addresses for the functions are dependant upon the Base Address of
the INX Panel.
For Further information on setting the Base Address of the INX Panel see Figure 11 DIP switch
address example on page 32.
6.4.1 Two Stage with Basic Reporting Addressing
To configure the recommended base address
To configure the INX for Two Stage with Basic Reporting in a Mircom system
To configure the INX for Single Stage with Basic Reporting in a Secutron system
Set DIP switch SW1 as: 0-0-0-1-1-0-1-0
OFF-OFF-OFF-ON-ON-OFF-ON-OFF
Set DIP switch SW2-1 to SW2-4 as: 0-0-1-0
OFF-OFF-ON-OFF
Set DIP switch SW2-1 to SW2-4 as: 0-1-1-0
OFF-ON-ON-OFF
Table 14 Configuring Two Stage Functions
Function Address Recommended
Address
Common Trouble Base Address 188
Signal Silence Base Address + 1 189
Activate NAC1, return NAC1 line status Base Address + 2 190
Activate NAC2, return NAC2 line status Base Address + 3 191
Activate NAC3, return NAC3 line status Base Address + 4 192
Activate NAC4, return NAC4 line status Base Address + 5 193
Activate NAC5, return NAC5 line status Base Address + 6 194
Second Stage NAC1 Base Address + 7 195
Second Stage NAC2 Base Address + 8 196
Second Stage NAC3 Base Address + 9 197
Second Stage NAC4 Base Address + 10 198
Second Stage NAC5 Base Address + 11 199