Specifications
51
Configuration
6.4.2 Two Stage Address Assignment with Enhanced Trouble Reporting
To configure the recommended base address
To configure the INX for Two Stage with Enhanced Trouble Reporting in a Mircom
System
To configure the INX for Two Stage with Enhanced Trouble Reporting in a Secutron
System
Set DIP switch SW1 as: 1-0-1-0-1-0-1-0
ON-OFF-ON-OFF-ON-OFF-ON-OFF
Set DIP switch SW2-1 to SW2-4 as: 0-0-0-0
OFF-OFF-OFF-OFF
Set DIP switch SW2-1 to SW2-4 as: 0-1-0-1
OFF-ON-OFF-ON
Attention: Two Stage Enhanced reporting is mandatory to meet ULC requirements.
Table 15 Configuring Two Stage Address Assignment with Enhanced Trouble
Reporting
Function Address Recommended
Address
Common Trouble Base Address 185
Signal Silence Base Address + 1 186
Monitor AC trouble Base Address + 2 187
Monitor Battery/Charger trouble Base Address + 3 188
Monitor Earth Ground Fault Base Address + 4 189
Activate NAC1, return NAC1 line status Base Address + 5 190
Activate NAC2, return NAC2 line status Base Address + 6 191
Activate NAC3, return NAC3 line status Base Address + 7 192
Activate NAC4, return NAC4 line status Base Address + 8 193
Activate NAC5, return NAC5 line status Base Address + 9 194
Second Stage NAC1 Base Address + 10 195
Second Stage NAC2 Base Address + 11 196