Specifications

58
Configuration
6.4.4 Two Stage Address Assignment with Enhanced Trouble Reporting and
Power Supply Addressing
In order to maximize the amount of addresses available, if a NAC circuit is configured as a
Power Supply, the next configured NAC Circuit is assigned the address reserved for the
previous Circuit.
Example Application
NAC 5 configured as a Power Supply.
INX-10A Common Trouble reporting address is 194.
To configure the recommended base address
To configure the INX for Two Stage with Enhanced Trouble Reporting in a Mircom
System
To configure the INX for Two Stage with Enhanced Trouble Reporting in a Secutron
System
To configure NAC 5 as a Continuous Power Supply
Attention: Two Stage Enhanced reporting is mandatory to meet ULC requirements.
Set DIP switch SW1 as: 1-1-1-0-1-0-1-0
ON-OFF-ON-OFF-ON-OFF-ON-OFF
Set DIP switch SW2-1 to SW2-4 as: 0-0-0-0
OFF-OFF-OFF-OFF
Set DIP switch SW2-1 to SW2-4 as: 0-1-0-1
OFF-ON-OFF-ON
Set DIP switch SW4-7 and SW4-8 as: 1-0
ON-OFF
!
SW1
1
8
234567
1
8
234567
SW2
ON
1
8
234567
SW2
ON
SW4
ON
1
8
234567