Specifications
59
Configuration
Table 17 Configuring Two Stage Address Assignment with Enhanced Trouble
Reporting and Power Supply Addressing
Function Address Recommended
Address
Common Trouble Base Address 187
Signal Silence Base Address + 1 188
Monitor AC trouble Base Address + 2 189
Monitor Battery/Charger trouble Base Address + 3 190
Monitor Earth Ground Fault Base Address + 4 191
Activate NAC1, return NAC1 line status Base Address + 5 192
Activate NAC2, return NAC2 line status Base Address + 6 193
Activate NAC3, return NAC3 line status Base Address + 7 194
Activate NAC4, return NAC4 line status Base Address + 8 195
Second Stage NAC1 Base Address + 10 196
Second Stage NAC2 Base Address + 11 197
Second Stage NAC3 Base Address + 12 198
Second Stage NAC4 Base Address + 13 199
Notes: Mircom recommends always using the upper range of addresses available for
the INX-10A.
Troubles occurring on a NAC circuit are only reported via the first stage address.
i