Wiring
7.2 Main Board Terminal Connections
Wire devices to terminals as shown below. See 7.1 Wiring Tables on page 67, Table 21 Wiring
Table for NAC and Auxiliary Power Circuits on page 67 and 9.0 Appendix A - Specifications
And Features - for more information.
Figure 29 Main Board Terminal Blocks
Attention: DO NOT exceed power supply ratings: Total current including Main
Chassis, AUX, and NAC circuits is 10A max.
Ground Fault Detection is required at all times. INX Ground fault detection
can only be disabled IF it is interfering the FACPs Ground Fault Detection
operation AND the FACP is used to manage the Ground Fault Detection.
Notes: The Terminal Blocks are depluggable for ease of wiring.
All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.