Table 23 INX-10A Specifications and Features
INX-10A Main Chassis
General Micro-controller based design, fully configurable from DIP Switches on front
panel.
NAC Circuits 5 Style Y or Z (Class B or A) configurable as strobes or audibles. Terminals are
labelled “NAC”.
Power limited / 24 VDC regulated / 2.5 A @ 49° C per Circuit
Aux. Power Supply. Terminals are labelled AUX PWR.
Power limited / 24 VDC Filtered (special application) / 1.7 A @ 49° C
Auxiliary relays
(resistive loads)
Must be connected to a Listed Power Limited Source of Supply. Terminals are
labelled “GROUND” and “TROUBLE”.
Ground Fault Form C, 1 Amp, 28 VDC
Common Trouble Form C, 1 Amp, 28 VDC
Electrical ratings AC line voltage 120V 60Hz / 240V, 50Hz
2 Amps / 1 Amp (primary)
NAC Circuits 24VDC regulated, Power Limited
10A Total, 2.5A maximum per circuit
Type 2 x 12VDC, Gel-Cell/Sealed Lead-Acid
Battery Charging capability 4Ah to 40Ah batteries
Current Consumption standby: 200 mA
alarm: 350 mA
Compliance System Model INX Addressable NAC Expander
Applicable Standards ULC S527-99, UL 864 R9 and UL
1481 R5