Use and Care Manual

Fire Wall Hangers
195
Copyright © 2020 MiTek Industries, Inc. All Rights Reserved
Fire Wall Hangers
MiTek
®
Product Catalog
FWH Fire Wall Hangers
Option
Skewed
1
Top Flange Offset
Range
1˚ to 70˚ --
1) Skewed hangers with skews greater than 15° may have all
joist nailing on outside flange.
Ordering
Add
SK,
angle required, right
(R)
or left
(L),
and square cut
(SQ)
to product number.
Ex. FWH3514_SK45R_SQ
Allowable Loads
80% of table load on skews up to 45°.
70% of table load on skews 46° to 70°.
Add
OS,
and
right
(R)
or left
(L),
to product number.
Ex. FWH3595_OSR
70% of table download.
180 lbs. Max uplift.
Type Qty Type
6 -- 10d 6 10d x 1-1/2 2240 180 2045 180 -- --
2 -- --
4
2980
3
380
6 -- 10d 6 10d x 1-1/2 2400 180 2400 180 -- --
2 -- --
4
2980
3
380
6 -- 10d 6 10d x 1-1/2 2400 180 2400 180 -- --
2 -- --
4
2980
3
380
6 -- 10d 6 10d x 1-1/2 2400 180 2400 180 -- --
2 -- --
4
2980
3
380
6 -- 10d 6 10d x 1-1/2 2400 180 2400 180 -- --
2 -- --
4
2980
3
380
1) Uplift Loads have been increased 60% for wind or seismic loads; no further increase shall be permitted.
2) Allowable downloads require at least one 2x stud at each hanger location and 4 face nails into 2-ply top plate.
3) FWH 1-9/16" wide hangers have an allowable download of 2,665 lb. at 100%, 2,765 lb. at 115% and 2,830 lb. at 125%.
4) Web stiffeners are required on I-Joist applications. Install per I-Joist manufacturer specifications.
5) NAILS: 10d x 1-1/2 nails are 0.148" dia. x 1-1/2" long, 10d nails are 0.148" dia. x 3" long.
New products or updated product information are designated in blue font.
2625
2625
2625
6
6 10d 6 10d x 1-1/2
6 10d 6 10d x 1-1/2
6 10d 6 10d x 1-1/2
Download
2
(100/115/125%)
Uplift
1
160%
380
380
380
2400
2400
2400
2400
DF Allowable Loads (Lbs.)
Solid Sawn
Header
2-Ply, 2x Wall
Top Plate
2-Ply 2x Wall Top Plate
with Stud Below
380
Download
(100/115/125%)
Uplift
1
160%
2625 380380
2625 380
2045
380
380
380
Without 5/8" gypsum
wallboard or structural
sheathing
After (1) layer of structural
sheathing & (1) layer of 5/8"
gypsum wallboard is installed
Two-sided after (2) layers of
5/8" gypsum wallboard
are installed (min. 2x6 wall)
After (2) layers of 5/8"
gypsum wallboard are
installed
After (1) layer of 5/8"
gypsum wallboard is installed
Fastener Schedule
5
Joist
10d 6 10d x 1-1/2
6 10d 6 10d x 1-1/2
Installation Type
Face
Qty
Header
Uplift
1
160%
Download
(100/115/125%)
Top
Qty
Specialty Options Chart – Refer to Specialty Options
pages 320 and 322 for additional details.
Typical FWH
stud wall installation
Typical FWH
stud wall with
(2) layers of 5/8" gypsum
wallboard installation
Typical FWH
solid sawn header installation
Fastener / Allowable Load Table